Product Manual
17/03/14 12030-GB
Technical data
TS 250 D
M
1.5
REV.0-03/14
Technical data TS 250 D
ALTERNATOR Self-excited,self-regulated,brushless
Type three-phase,asynchronous
Insulating class H
GENERATOR
Three-phase generation 6.5kVA/400V/9.4A
Single-phase generation 4.5kVA/230V/19.5A
Single-phase generation 2kVA/48V/41.6A
Frequency 50Hz
ENGINE
Mark / Model KohlerKD477/2
Type / Cooling system Diesel4-Stroke/air
Cylinders / Displacement 2/954cm
3
Netoutput 14.9kW(20.3HP)
Speed 3000rpm
Fuel consumption (Welding 60%) 1.7l/h
Engine oil capacity 3l
Starter electric
GENERAL SPECIFICATIONS
Tank capacity 9l
Running time (Welding 60%) 5.3h
Protection IP23
*Dimensions Lxwxh (mm) * 1050x530x630
*Weight 200Kg
**Acoustic power LwA (pressure LpA) 103dB(A)(78dB(A)@7m)
* Dimensions and weight are inclusive of all parts without wheels and towbar ** For xed installation only.
POWER
Declared power according to ISO 3046-1 (temperature 25°C, 30% relative hummidity, altitude 100 m above sea level).
It’s admitted overload of 10% each hour every 12 h.
In an approximative way one reduces: of 1% every 100 m altitude and of 2.5% for every 5°C above 25°C.
ACOUSTIC POWER LEVEL
ATTENTION: The concrete risk due to the machine depends on the conditions in which it is used. Therefore, it is up to the end-
user and under his direct responsibility to make a correct evaluation of the same risk and to adopt specic precautions (for
instance, adopting a I.P.D. -Individual Protection Device)
Acoustic Noise Level (LWA) - Measure Unit dB(A): it stands for acoustic noise released in a certain delay of time. This is not
submitted to the distance of measurement.
Acoustic Pressure (Lp) - Measure Unit dB(A): it measures the pressure originated by sound waves emission. Its value changes
in proportion to the distance of measurement.
The here below table shows examples of acoustic pressure (Lp) at different distances from a machine with Acoustic Noise Level
(LWA) of 95 dB(A)
Lp a 1 meter = 95 dB(A) - 8 dB(A) = 87 dB(A) Lp a 7 meters = 95 dB(A) - 25 dB(A) = 70 dB(A)
Lp a 4 meters = 95 dB(A) - 20 dB(A) = 75 dB(A) Lp a 10 meters = 95 dB(A) - 28 dB(A) = 67 dB(A)
PLEASE NOTE: the symbol when with acoustic noise values, indicates that the device respects noise emission limits
according to 2000/14/CE directive.
2000 / 14 /CE