Product Manual
USE AS A GENERATOR
M
37
REV.0-06/99
Sockets are not self-locked: tension is avaible
immediately after starting also with no plug.
WARNING
☞
It is strictly forbidden to connect the group
to the public mains a/o to another source of
electric power.
The replacement of the fuse must absolutely be
done with the engine off (remove the mechanical
protection, then shift down the small lever of the
fuse holder placed on the front panel).
CAUTION
☞
At the beginning of every work, check the
electric parameters and/or the controls placed
on the front.
Make sure the unit is properly grounded (12) (where
it is assembled).
- See page M20, 21, 22, 25, 26, 27 -.
Move the accelerator lever (16) and reach the engine
maximum speed, except for the engines with
constant rpm; the voltmeter (N) (where it is
assembled) shows the single-phase voltage whether
three or single-phase current has to be drawn.
*N.B.: with electronic tens. regul. RVT ±1%
Connect up the machine, using proper plugs and
cables in good condition to the AC socket (15) to
draw single or three-phase power, or, by cables
with adeguate section, to the terminal board, placed
inside the derivation box (Q3).
Nominal
voltage
110V
230V
230V
400V
asynchronous
±10%
±10%
±10%
±10%
synchronous (*)
±5%
±5%
±5%
±5%
Indicative no-load voltage
The areas, access of which is forbidden to
unqualified personel, are:
- the control switchboard (front), the exhaust of
the endothermic engine.
WARNING
The warning light (L), located near the current
socket, lights up when the unit can supply alternated
current, on condition that the engine is at the
maximum rpm.
☞
N.B.: if the warning light does not flash, check
the accelerator which must bebat its
maximum, or the fuse of the relevant
socket (single-phase) or the thermopro-
tection.
Using several sockets at tha same time, the
maximum power possible is that indicated on the
data plate.
To draw power simultaneously in the WG welder
version see page M52.
The max. continuous power of the generating set or
theload current must not be exceeded.
MACHINE WITH THERMOPROTECTION
If you overload the genset the thermoprotection will
automatically switch off.
lf the thermoprotection is released, disconnect all
the connected loads.
Reset the thermoprotection pressing the central
pole.
When reset, connect the loads again.
In case the protection should act furtherly, check:
the connections, the wires or others, and if
necessary call the Assistance Service.
AvoId to hold the central
pole of the
thermoprotection
pressed for a long time.
Otherwise, in case of trouble, it will not click,
damaging the generating set.
CLOSED OPEN
16/06/99 M37-GB
PRESS TO
RESET