5.2. Installation in front of or to the side of a wall to be protected
2 Insulation layer (Flue)
3 Connection piece
4 Insulation layer (Back wall)
5 Convection space
6 Fresh air intake
7 Concrete plate min. 6 cm (only
when installing on a oor to be protected)
8 Ceiling
9 Insulation layer (Floor)
10 Combustion air pipe
11 Covering (Out towards the room)
12 Insulation layer (Ceiling)
13 Supply air grille
14 Circulation air grille
15 Protective shield for oors made of
non-ammable material
16 Insulation layer (Side wall)
17 Covering (Out towards the room)
18 80 cm radiation area
19 Convection air box
20 Wall to be protected
21 Fire protection at the ue lead-through
22 Front walling min. 10cm
5.3. Convection space
Without the convection box (accessory), there must be at least 6 cm
between the replace inset and insulation (4,16) at the back wall and
both sides.
• The convection areas (5) must have heat protection on all surfaces
that are not a heat-emitting lining.
• The replace walls, oor and ceiling must be clean and resistant to
wear (see professional rules for stove and air source heating technolo-
gy). Otherwise, the insulation must be protected with a wear-resistant
material (radiation plate / replace inset plate etc.).
4
22
5
Convection air supply with convection box
All convection air supplies must be made from rigid, non-ammable material.
The hot air pipe must be secured to the supply air pipe and air grates (preferably with a
metal pipe).