5.12. Ceiling above the Insert
- If the cavity above the replace inset reaches up to the ceiling
(8), it must be protected, if:
- it consists of ammable material,
- there is a supporting element in the building.
Insulation (G) must be installed to local/national requirements/
standards (11).
5.13. Floor in front of the inset
- The oor in front of the inset must comprise a non-ammable material. The minimum
dimension for the area is:
In front:
- the distance between the oor and lower edge of the combustion chamber plus 30
cm, however at least 50 cm.
To the sides:
- the distance between the oor and lower edge of the combustion chamber plus 30
cm, however at least 30 cm.
5.14. Fire safety in the radiation area
- There must be a safety distance to ammable material on each side of and above the
inset’s door of at least 80 cm. If ventilated radiation protection is present on each side, a
distance of 40 cm is enough.
5.15. Fire safety outside the radiation area
There must be a distance of at least 5 cm between the inset’s outer wall and ammable
material such as furniture or other ammable materials. There must be sucient odour
ow-through in this gap to prevent any unpleasant odours. Building materials that com-
prise only a small part of the inset’s lining, such as oor, wall lining,
and insulation on the ceiling/walls, can be tted directly around the inset’s lining.
5.16. Electrical cables
The walls and ceiling near to the inset must not contain electrical wires!