Instructions

40
Sprog
5.7. Expansion seams
- There must be NO contact/connection between the inset and the lining (11)! There-
fore, all places of contact between the inset and lining must be shielded with a sealing
cord (Glass bre).
The support frame (23) must not rest on the insert or be screwed or welded to it!
5.8. Wall lining
- The lining room-side (11) must be made from non-ammable material to building ma-
terial class A1, for example brick, ceramic chips, metal and plaster.
- Beams (24) in front of the lining (11) and sup-
port frame (23) next to the open replace are
permitted at a distance of at least 1 cm, when:
- the beams are not part of the building
- the clearance to the lining (11) is open enough
that heat does not accumulate
- the beams are not in the open replace’s ra-
diation area.
- Direct fastening with heat bridges is not per-
mitted.
5.9. Decorative beams
(F) Expansion joint (24) Beam
(23) Support frame (11) Lining
5.10. Chimney lining
- The chimney lining (11) must not be in direct contact with the replace insert. It must
be self-supporting. The manufacturers oer various support frames for this purpose
(23).
5.11. Convection air supply
- The cross-section of the air inlet (14) and air outlet guide
must each be at least 700 cm².
- It must not be possible to close o at least 200 cm² of the
air inlet and air outlet opening.
- There must not be any ammable building material, e.g.
wood ceiling or furniture, within a distance of 30 cm of the
side of the air outlet and 50 cm above the air outlet (13).