Instructions
39
Sprog
5.4. Heat insulation on the side and back wall
(All values in accordance with Promasil 950 KS)
• The front walling (22) and building’s wall (20) must be protected with a layer of insu-
lation (4,16) to the back and side of the replace. Thermal insulation, see point 3 techni-
cal data.
• The lining (11) must also be protected with a layer of insulation. The lining does not
need to be protected when the replace is designed such that the temperature of the
lining’s free surfaces and niches for storing wood do not exceed max. 85° C. For sur-
faces made of mineral material, e.g. tiles, apart from where objects/things are to be
stored/place, a max. temperature of 120 °C applies instead of 85 °C. The rise in the
maximum permitted temperature from 85 °C to 120 °C applies only to more steep or
vertical surfaces of linings made from mineral material. This enables the lining such as
heat-emitting tile walls or similar to be extended.
5.5. Front walling
- There must be a 10 cm-thick (measurement C) mineral front wal-
ling (22), e.g. Poroton stone, between the insulation (4) and wall
(20). The front walling must extend at least 20 cm above the con-
nection piece (3).
- Front walling (22) can be avoided if the wall (20) :
- is at least 10 cm thick and
- comprises non-ammable material and
- is not a supporting concrete or steel structure
5.6. Protecting the oor
- Floors (8) made of ammable material must be protected as follows:
- by a concrete plate (6) at least 6 cm (measurement E) thick, taking into account
the oor’s carrying capacity. An insulation layer (9) must be laid on top (measure-
ment D). For insulation layers see point 3. - technical data.
- Supporting concrete or steel oors (8) must be protected as follows:
- Heat insulation layer (9) - min. thickness, see point 3 - technical data.










