Instructions

34
Sprog
2.5 Connection pieces/Flue
The connection pieces/ue must be dimensioned to DIN EN 13384.
They must be steel pipe with a min. thickness of 2 mm. Austenitic, stainless steel needs
to be only 1 mm thick.
The connection piece is connected directly to the chimney.
The connection piece inside the replace structure must be min. 3 cm thick, rigid and
made from non-ammable insulation material of class A1 in accordance with DIN 4102
and covered with an insulating layer.
This does not apply to connection pieces used for heating convection air and where the
risk of re is otherwise excluded.
3. Technical data
4. Chimney and replace measurement data
Too much draught in the chimney must be restricted.
The dealer or chimney sweep must ensure/test for the correct draught.
For draughts of more than 18 Pa, we recommend installing a regulating damper (avai-
lable as an accessory) in the ue outlet!