TriStar MPPT 600V Installation & Operation Manual

72 Specications
9.0 Specications
Electrical
TS-MPPT-60-600V-48 TS-MPPT-60-600V-48-
DB
Nominal System Voltage 48 volts 48 volts
Maximum Battery Current 60 amps 60 amps
Maximum Solar Input Voltage 600 volts dc 600 volts dc
Battery Operating Voltage Range 16 - 72 volts dc 16 - 72 volts dc
Nominal Maximum Input Power* 3200 watts 3200 watts
Voltage Accuracy ≤0.1%±100mV ≤0.1%±100mV
Self consumption (tare loss) 2-3.5 watts 2-3.5 watts
Transient Surge Protection 4500 watts / port 4500 watts / port
*ThesepowerlevelsrefertothemaximumwattagetheTS-MPPT-60-600V-48canprocess.Higherpowerarrayscanbeused
withoutdamagingthecontroller,butarraycost-benetwillbereducedatpowerlevelsmuchbeyondthenominalrating.
Battery Charging
Charging algorithm 4 - stage
Charging stages Bulk, Absorption, Float, Equalize
Temperaturecompensationcoefcient -5mV/°C/cell(25°Cref.)
Temperature compensation range (RTS connected) -30 °C to +80 °C
Temperaturecompensatedset-points Absorption,Float,Equalize,HVD
Charging Set-points:
Settings
Switches
Battery
Type
Absorp.
Stage
Float
Stage
Equalize
Stage
Absorp.
Time
Equalize
Time
Equalize
Timeout
Equalize
Interval
sw: 4-5-6 Volts Volts Volts Minutes Minutes Minutes Days
off-off-off 1 - Sealed* 56.00 54.80 150
off-off-on 2 - Sealed* 56.60 54.80 57.60 150 60 120 28
off-on-off 3 - Sealed* 57.20 54.80 58.40 150 60 120 28
off-on-on 4 - AGM/Flooded 57.60 54.80 60.40 180 120 180 28
on-off-off 5 - Flooded 58.40 54.00 61.20 180 120 180 28
on-off-on 6 - Flooded 58.80 54.00 61.60 180 180 240 28
on-on-off 7 - L-16 61.60 53.60 64.00 180 180 240 14
on-on-on 8 - Custom Custom Custom Custom Custom Custom Custom Custom
* “Sealed” battery type includes gel and AGM batteries
See section 4.2 for more information
NOTE:
All charging voltage set-points listed are for 48 Volt systems.