TriStar MPPT 600V Installation & Operation Manual

65TriStar MPPT 600V Operator’s Manual
• Déconnectez toutes les sources d’alimentation du contrôleur avant d’installer ou de régler
le TriStar MPPT.
• Le TriStar MPPT ne contient aucun fusible ou interrupteur. Ne tentez pas de réparer.
Installation Safety Precautions
WARNING:
This unit is not provided with a GFDI device. This charge controller must be used with an
external GFDI device as required by the Article 690 of the National Electrical Code for
the installation location.
• Mount the TriStar MPPT 600V indoors. Prevent exposure to the elements and do not allow
water to enter the controller.
• Install the TriStar MPPT 600V in a location that prevents casual contact. The
TriStar MPPT 600V heatsink can become very hot during operation.
• Use insulated tools when working with batteries.
• Avoid wearing jewelry during installation.
• The battery bank must be comprised of batteries of same type, make, and age.
• Do not smoke in the vicinity of the battery bank.
• Power connections must remain tight to avoid excessive heating from a loose connection.
• Use properly sized conductors and circuit interrupters.
• Thegroundingterminalislocatedinthewiringcompartmentandisidentiedbythesym-
bol below.
Ground Symbol
• This charge controller is to be connected to DC circuits only. These DC connections are
identiedbythesymbolbelow.
Direct Current Symbol
TheTriStarMPPT600Vcontrollermustbeinstalledbyaqualiedtechnicianinaccordancewith
electrical regulations of the country where the product is installed.