TriStar MPPT 600V Installation & Operation Manual

47TriStar MPPT 600V Operator’s Manual
4.3 Push-Button
The following functions can be enabled with the pushbutton (located on the front cover):
PUSH
• Reset from certain errors or faults.
• Reset the battery service indication if this has been activated in custom settings. A new
serviceperiodwillbestarted,andtheashingLEDswillstopblinking.Ifthebatteryser-
vice is performed before the LEDs begin blinking, the pushbutton must be pushed at the
time when the LEDs are blinking to reset the service interval and stop the blinking.
PUSH AND HOLD 5 SECONDS
• Request battery equalization manually. The TriStar MPPT 600V will begin equalization
in either the manual or automatic equalization mode. Equalization will begin when there
issufcientsolarpowertochargethebatteryuptotheequalizationvoltage.TheLEDs
willblinkthesequencedenedintable4-3belowtoconrmthatanequalizehasbeen
requested. The equalization request will automatically stop per the battery type selected
(see Section 4.2). Equalization will only occur if the selected battery type has an equaliza-
tion stage.
• Stop an equalization that is in progress. This will be effective in either the manual or auto-
maticmode.Theequalizationwillbeterminated.TheLEDswillblinktoconrmtheequal-
ize has been cancelled as shown in table 4-3 below.
Push-Button Action SOC LED Indication
Manual Equalization Started Green+Yellow+Red / Green+Yellow+Red / Green / Green
Stop Equalization Green+Yellow+Red / Green+Yellow+Red / Red / Red
Table 4-3. Manual Equalization LED Indcations
NOTE:
For multiple TriStar MPPT 600V controllers on a MeterBus
TM
network, initialize a battery
equalization using the TriStar meter so that all controllers are synchronized.
REMARQUE :
Avec plusieurs contrôleurs TriStar MPPT sur un réseau MeterBusTM, initialisez une
compensation de batteries à l’aide de l’outil de mesure TriStar an de synchroniser tous les
contrôleurs.
Note that if two or more TriStar MPPT 600V controllers are charging in parallel, each controller
may attempt to equalize on a different day. Systems with multiple controllers should only equalize
manually to ensure synchronization between controllers.