28
Installation
Over-Current Protection and Disconnects
WARNING: Shock Hazard
Fuses, circuit breakers, and disconnect switches should never
open grounded system conductors. Only GFDI devices are
permitted to disconnect grounded conductors.
AVERTISSEMENT : Risque de décharge électrique
Les fusibles, coupe-circuits et interrupteurs ne doivent jamais
ouvrir les conducteurs du système mis à la terre. Seuls les
dispositifs GFDI sont autorisés à déconnecter les conducteurs
reliés mis à la terre.
The battery circuit fuse or circuit breaker must be rated to 125% of the maximum current or more
unless the device is UL listed for 100% continuous rating. The minimum fuse/breaker rating al-
lowed for use with each TriStar MPPT 600V model is:
1.25 x 60 Amps = 75 Amps
A disconnect is required for the battery and solar circuits to provide a means for removing power
from the TriStar MPPT 600V.
Connect the Power Wires - TS-MPPT-60-600V-48
WARNING: Shock Hazard
The solar PV array can produce open-circuit voltages in excess of 500 Vdc when
in sunlight. Verify that the solar input breaker or disconnect has been opened
(disconnected) before installing the system wires.
AVERTISSEMENT : Risque de décharge électrique
Le réseau PV solaire peut produire des tensions de circuit ouvert supérieures à 500 V cc
à la lumière du soleil. Vériez que le coupe-circuit ou l’interrupteur d’entrée solaire a été
ouvert (déconnexion) avant d’installer les câbles du système.