TriStar Manual

58 Specications
8.0 Specications
Electrical
TS-MPPT-30 TS-MPPT-45 TS-MPPT-60
Nominal System Voltage All: 12, 24, 36, or 48 Volts dc
Maximum Battery Current 30 Amps 45 Amps 60 Amps
Maximum Solar Input Voltage All: 150 Volts dc
Battery Operating Voltage Range All: 8 - 72 Volts dc
Nominal Maximum Input Power*
12 Volt 400 Watts 600 Watts 800 Watts
24 Volt 800 Watts 1200 Watts 1600 Watts
48 Volt 1600 Watts 2400 Watts 3200 Watts
Voltage Accuracy
12/24V:≤0.1%±50mV
48V:≤0.1%±100mV
Self consumption (tare loss) All: 1.3 - 2.7 Watts
Transient Surge Protection All: 4500 Watts / port
* These power levels refer to the maximum wattage each of the TS-MPPTs can process at a certain system voltage. Higher
powerarrayscanbeusedwithoutdamagingacontroller,butarraycost-benetswillbereducedatpowerlevelsmuchbeyond
the nomina l ra tings.
Battery Charging
Charging algorithm 4 - stage
Charging stages Bulk, Absorption, Float, Equalize
Temperaturecompensationcoefcient -5mV/°C/cell(25°Cref.)
Temperature compensation range -30 °C to +80 °C
Temperature compensated set-points Absorption, Float, Equalize, HVD
Charging Set-points:
Settings
Switches
Battery
Type
Absorp.
Stage
Float
Stage
Equalize
Stage
Absorp.
Time
Equalize
Time
Equalize
Timeout
Equalize
Interval
sw: 4-5-6 Volts Volts Volts Minutes Minutes Minutes Days
off-off-off 1 - Sealed* 14.00 13.70 150
off-off-on 2 - Sealed* 14.15 13.70 14.40 150 60 120 28
off-on-off 3 - Sealed* 14.30 13.70 14.60 150 60 120 28
off-on-on 4 - AGM/Flooded 14.40 13.70 15.10 180 120 180 28
on-off-off 5 - Flooded 14.60 13.50 15.30 180 120 180 28
on-off-on 6 - Flooded 14.70 13.50 15.40 180 180 240 28
on-on-off 7 - L-16 15.40 13.40 16.00 180 180 240 14
on-on-on 8 - Custom Custom Custom Custom Custom Custom Custom Custom
* “Sealed” battery type includes gel and AGM batteries
See section 4.2 for more information
NOTE:
All charging voltage set-points listed are for 12 Volt systems.
Multiply 2X for 24 Volt systems, 4X for 48 Volt systems.