SunSaver MPPT Installation and Operation Manual
MORNINGSTAR CORPORATION 7
1.0
Installation Safety Precautions
WARNING:
This unit is not provided with a GFDI device. This
charge controller must be used with an external
GFDI device as required by the Article 690 of
the National Electrical Code for the installation
location.
• Mount the SunSaver-MPPT indoors. Prevent exposure to the
elements and do not allow water to enter the controller.
• Install the SunSaver in a location that prevents casual contact.
The SunSaver heatsink can become very hot during operation.
• Use insulated tools when working with batteries.
• Avoid wearing jewelry during installation.
• The battery bank must be comprised of batteries of same type,
make, and age.
• Do not smoke in the vicinity of the battery bank.
• Mount the controller at least 3 ft (1 m) away from vented bat-
teries unless separated by a barrier or located in a separate
compartment.
• Power connections must remain tight to avoid excessive heating
from a loose connection.
• Use properly sized conductors and circuit interrupters.
• This charge controller is to be connected to DC circuits only.
These DC connections are identied by the symbol below.
Direct Current Symbol