5.0 TROUBLESHOOTING
MORNINGSTAR CORPORATION 33
5.0
4.7 Programming Custom Setpoints
!
CAUTION: This feature should only be used by advanced
users who have very specifi c charging and/or load
control requirements that are not met using the factory
default charge and load control settings. The factory
default settings will be suffi cient for the vast majority of
users.
Custom charging and load setpoints can be programmed into SS-
MPPT non-volatile memory using a PC with Morningstar MSView
software installed and a Meterbus to Serial Adapter (model: MSC).
Refer to the MSView help fi les for detailed instructions. MSView PC
software is available for free on our website at:
http://www.morningstarcorp.com/
A setup wizard will guide you through the setpoint confi guration
process. Refer to MSView help fi les for more information.
To use custom setpoints, the Settings Switches must be adjusted as
follows:
SWITCH #1 ON (↑) TO USE CUSTOM CHARGING SETPOINTS.
USE THE BATTERY SELECT JUMPER TO SELECT BETWEEN
TWO SETS OF CUSTOM CHARGING SETPOINTS.
SWITCH #2 ON (↑) TO USE CUSTOM LOAD CONTROL
SETPOINTS.
NOTE: Programming custom setpoints will overwrite the
default Gel and AGM battery type values programmed
into custom memory at the factory. Document the new
custom values in this manual for future reference.
5.0 Troubleshooting
5.1 Error Indications
NOTE: If an optional Morningstar Remote Meter is
attached to the SunSaver MPPT , use the self-diagnostic
feature to determine the cause of the error indication.
Refer to the Remote Meter Operator’s Manual for more
information.
Status LED Error Indications
PV High Voltage Disconnect Flashing Red•
RTS Shorted Flashing Red•
RTS Disconnected Flashing Red•
Damaged local temp. sensor Solid Red•
1
Damaged heatsink temp. sensor Solid Red•
1
Damaged input MOSFETs Solid Red•
1
Firmware Error Solid Red•
1
1 - heartbeat indication flickers the Status LED off briefly every 5 seconds
Battery Status LED Error Indications
Load High Voltage Disconnect R-G Sequencing•
High Temperature Disconnect R-Y Sequencing•
Remote Temp. Sensor Error Y/R - G/Y Sequencing•
External Wiring Error G/R-Y Sequencing•
Load Overcurrent Y/R-G Sequencing•
Load Short Circuit G/R-Y Sequencing•
Custom Setpoints Update G/Y/R Flashing•
Self-test Error R-Y-G Sequencing•