7.2.4. Battery installation example 2
This example provides excellent mechanical protection for
batteries and ensures safe seismic restraint.
Ventilation slots at ground level on the front and at the top of
the lid behind the hinge provide through flow ventilation so
any hydrogen gas produced can rise easily up and away from
the batteries.
Ideally the lid should be slanted to prevent incidental use of
the lid as a shelf. (Objects will slide off).The use of a child
proof catch and signage on the outside (top) of the lid is also
required.
7.2.5. Battery installation example 3
This example inside a shipping container
provides excellent mechanical protection for
batteries and ensures safe seismic restraint.
Note:
Safety signs
Fire extinguisher
Battery maintenance kit
Battery top up water
Seismic restraints
Large ventilation grates at ground level and at the top of the
container provide through flow ventilation.
Heavy container doors are locked ensuring no unauthorized
access.
7.2.6. Battery installation example 4
Battery box close to inverter system in a hydro
solar hybrid system comprising:
Battery bank - 3 x 48 VDC strings of 400
amp hours.
7kW Outback Radian inverter system
5.25kW solar PV array on roof via FM80
1.5kW hydro via FM80
The battery enclosure is externally vented and
lockable.