Installation manual
© 2014 EcoInnovation Ltd (NZ) Page 83
The 3-pole HRC fuse holders can serve a multi-purpose of providing
current protection for each battery string (maybe required by
regulation in some jurisdictions), act as a combiner for multiple
strings and act a busbar termination point for other connections
needed in the system.
The picture on the right shows a HRC 3-pole fuse holder with a top
combiner link and busbar for 3 battery strings.
Where 1-2 battery strings are used the spare position in the 3-pole
HRC fuse holder can be employed to break the incoming hydro
cable connection and replace SB2 or DB2. This then provides a
single point of system shutdown, which is regarded as best practice.
Label
“In emergency pull this handle for complete system shut down”
There is another possible option for 1 battery string, in this case the battery + and battery –
fuses are in the same 3-pole HRC holder. The spare 3rd fuse position (normally the middle
position) can be used for the incoming hydro generation.
6.8.1. Important note when MPPT controllers are not used
Over the years we have seen the electronics of many systems killed by incorrect
connection of the hydro turbine. If you wire your PowerSpout turbine directly to
your battery system (no MPPT between) and do not follow our advice below, then
it is important to reiterate that you do not want the main battery fuse to blow or
be removed with the turbine running, because the battery is the primary protection against
over-voltage in the system. The hydro turbine's open circuit voltage will likely destroy all of
your electronics in the event of the fuse blowing.
PowerSpout turbines PLT/TRG 14/28/56 (non-MPPT turbines). The positive wire should be
wired to its own HRC battery fuse, as shown in the diagram. If the HRC fuse is opened
(while the turbine is still running) then the turbine will produce a higher voltage but it will be
isolated from the electronics. It is not possible to wire each battery string to its own fuse in
this situation, but it is more important to separate the turbine from the electronics when the
battery isolator is operated.
6.8.2. Important note on cable sizing
If a breaker is omitted then the cable is still protected by the battery fuse, but this is often too
large. Any unprotected cables must be sufficiently large to safely handle the full short circuit
current if breakers are omitted. We do not advise that you omit breakers.
Cable sizes need to be adequate for the circuit protection in each case.