Installation manual

© 2014 EcoInnovation Ltd (NZ) Page 69
Common sizes are:
10 Amp
16 Amp
20 Amp
25 Amp
32 Amp
40 Amp
50 Amp
63 Amp
Common brands that are widely used include: Noark, Schneider and ABB.
6.2. DC Earthing/grounding explained
Earthing (aka grounding) is done to protect against electric shock hazard. It also helps to
protect against equipment damage from lightning-induced voltage surges in the system.
There is much confusion about what earthing means. The words can mean any of 3 things:
1. Earth electrode: Connecting something to an earth rod or buried conductors.
2. Equipment earthing: Connecting all metal exposed parts to protective "earth" wires
that "bond" cases, conduit, hydro bulkhead etc. together (and to earth).
3. System earthing: Connecting one pole of the supply (for example the DC negative) to
the earth wiring. The earthed pole is known as the neutral pole.
6.2.1. Earth electrode or earth rod
Generally only one wire should go to your earth rod (or
rods). If earth wires need to be combined prior to the
earth rod this is done with an earth busbar in a suitable
enclosure.
Simply connecting something to an earth rod will not automatically make it safe unless you
have a "residual current device" to detect small leakages. An earth rod usually has a
relatively high impedance (resistance). Any small fault current in an earth rod is unlikely to
trip a circuit breaker or to blow a fuse, hence alerting the user to the fault. A very low
resistance earth electrode would be needed to ensure safety if things are not hard-wired to
each other using equipment earth wiring as below. Connecting an earth rod in no way
replaces proper bonding of external metallic parts that could give you a shock due to
differences in voltage between them.
6.2.2. Equipment earthing
For the purpose of this manual, earthing of exposed metal (equipment earthing) is always
required, (but follow your local rules). Use protective conductors (called earth wires) to join
all exposed metal objects together. Make sure you establish a good electrical “bond” that
can last the lifetime of the system. Read the equipment instruction manuals to see what is
recommended. Check local regulations for sizes, these will generally be 4mm
2
green
insulated copper wire. If your battery bank is earthed then a heavy wire is required to make
this connection normally 16-50mm
2
or larger. Earth wiring must be able to safely carry
heavy fault currents in the event that a live wire touches the case of an item of equipment.
Bonding items to each other protects people and livestock against getting a shock from
touching two items that might accidentally have a dangerous voltage between them. A fault