Installation manual
© 2014 EcoInnovation Ltd (NZ) Page 49
Once the controller recognizes that your battery charge rate has reached the highest safe
level it diverts any additional incoming power to a diversion load. Such controllers normally
allow you to set the voltage threshold at which power diversion starts according to the type
of battery in use. This threshold will also be automatically adjusted for the stages of battery
charging (absorb, equalise, float) and the battery temperature.
A non-MPPT controller should never be placed between the hydro turbine and
the battery. This is normal practice for solar PV and a battery only. Many clients
new to hydro think the same applies for hydro - it does not. Installing a solar
controller that is not designed for MPPT between the turbine and the battery will
usually destroy the controller through the hydro's high Voc off load.
Low cost solar controllers are NOT suitable for micro-hydro and wind applications as they do
not have a diversion mode option.
5.6.1. Multiple energy sources and diversion load controllers
A PowerSpout turbine can charge the same battery as a solar PV array, wind turbine and/or
other sources. This is a very normal arrangement, with many advantages for the user.
Diversion load controllers need to be sized large enough to divert all of the current from all
unregulated sources (such as direct-connected hydro and wind turbines).
If your solar system has its own controller then the diversion controller can work alongside
this but you may see some error indications on one of the two controllers as they are unlikely
to exactly agree on the best charging voltage. This need not be a problem so long as the
battery charge rate is effectively regulated.
When charging the battery from an engine driven generator you may find that the energy is
being diverted into a heater by the controller. If this is unwelcome (waste of fuel) then you
may need to adjust downward the charge voltage settings of your inverter/charger unit so
that the diversion control is not triggered. It's also possible to use a relay on the generator
output to modify the 'battery sensing' voltage to the controller so as to defeat it during
generator operation.
5.6.2. Backup diversion load controller
A secondary or backup controller is recommended in all hydro energy
systems where the turbine connects directly to the battery. Since PWM
controllers are relatively inexpensive components, redundancy will protect
the higher value components in your system in the event of failure of the
primary controller.
This picture illustrates two PWM controllers and their diversion
resistors. If there is a controller failure, the expensive battery
bank will remain protected from overcharging. Over-charging
batteries can dry out and even explode if the problem is not
recognised. Check controller operation on a regular basis by
monitoring the battery voltage and electrolyte levels and
observing the indicator lamps and load temperature.