FEB-20E UK ECOPLUS USER INSTRUCTIONS AND TECHNICAL INSTRUCTIONS
CONTENTS Section Page 1 USERS INSTRUCTIONS 3 2 GENERAL SPECIFICATIONS 6 3 TECHNICAL DATA 9 4 GENERAL INSTALLATION REQUIREMENTS 10 5 INSTALLATION INSTRUCTIONS 14 6 COMMISSIONING INSTRUCTIONS 17 7 ROUTINE SERVING INSTRUCTIONS 19 8 WIRING DIAGRAMS 21 9 FAULT FINDING 22 2
1.- USERS INSTRUCTIONS 1.1.- GAS SAFETY (INSTALLATION AND USE) REGULATIONS 1996 (AS AMENDED) It is the law that all gas appliances are installed by a registered person, in accordance with the above regulations. Failure to install appliances correctly could lead to prosecution. It is in your own interest, and that of safety, to ensure that the law is complied with. WARNING: It is essential that the appliance is correctly earthed. An electricity supply of 230 V 50 Hz is required, fused at 3 Amp.
1.5.- HOT WATER AND CENTRAL HEATING SERVICE Turn the main control switch to the winter setting. The burner will automatically fire up. By means of the central heating temperature selector control knob,any water temperature of between 60 and 85°C may be selected. The boiler will remain on until the temperature selected on the room thermostat or on the boiler itself is reached. Whenever there is a demand for D.H.W. from the central heating setting, the boiler is ready to supply it giving priority to the D.H.
APPLIANCE SAFETY LOCK-OUT This boiler has a cut-out indicator built in to it. Whenever a malfunction is detected in the ignition of the boiler, the boiler switches off automatically and the cut-out indicator lights up (red indicator light) To reset the boiler press the restart switch. The red indicator light should go out.
2.- GENERAL SPECIFICATIONS The Fagor FEB-20E is a wall hung, room sealed, fan assisted, microprocessor controlled fully modulating gas combination boiler for providing both central heating and domestic hot water. It is particularly suitable for Caravan Holiday Home and Park Home use. Maximum heat output in either heating or hot water mode is 23.7.kW (80.840 Btu/h), and priority is always given to the supply of hot water.
1 11 2 3 4 12 5 6 13 14 15 7 16 8 9 17 10 18 Principal components 1. Back Plate 2. Automatic Air Vent 3. Air pressure switch 4. Heating Thermistor 5. High limit stat 6. Ionisation electrode 7. Main Burner 8. Circulation Pump 9. Flow switch 10. Pressure relief valve 11. Fan 12. Heat Exchanger 13. Combustion Chamber 14. Expansion Vessel 15. Ignition electrode 16. Domestic Hot Water Thermistor 17. Gas Valve 18.
Schematic diagram- Hydraulic circuit 29 1.- Heat exchanger 31 30 27 2.- Ignition Electrode 1 3.- Detection electrode 5.- Burner 26 6.- Injector Manifold 2 25 7.- D.H.W Thermistor 24 5 8.- Burner pressure nipple 3 9.- Gas valve 23 6 10.- Inlet pressure nipple 11.- Gas inlet 7 13. D.H.W outlet 22 8 16 14.- Heating flow 16.- Flow switch 9 17.- Water filter 21 20 19 18 18.- Cold water inlet 19.- By-pass 10 17 14 13 11 3 2 25.- Expansion vessel 20.- Heating return 26.
3.- TECHNICAL DATA Model Category Type Maximum Output Central Heating (C.H) Output Minimum Output Maximum Output Domestic Hot Water (D.H.W.) Output Minimum Output Qn max. Qn min. Central Heating Nominal Heat Input (Hi) and D.H.W. Nominal Heat input (Hi) kW kcal/h kW kcal/h kW kcal/h kW kcal/h kW kW D.H.W. Flow Rate at 25º C Temp Rise (l/min) D.H.W. Nominal Flow (l/min) 10 Minimum Flow Rate Required to Activate D.H.W. Mode (l/min) Maximum C.H. Operating Pressure (bar) Maximum D.H.W. Minimum D.H.W.
4.- GENERAL INSTALLATION REQUIREMENTS 4.1 STATUTORY REQUIREMENTS GAS SAFETY (INSTALLATION AND USE) REGULATIONS 1998 (As amended). It is the law that all gas appliances must be installed by a registered person, in accordance with the above regulations. Failure to install appliances correctly could lead to prosecution. It is in your own interest, and that of safety, to ensure that the law is complied with.
4.3 FLUE TERMINAL POSITION - The boiler MUST be installed so that the terminal is exposed to the external air. - It is important that the position of the terminal allows free passage of air across it at all times. - It is ESSENTIAL TO ENSURE, in practice that products of combustion discharging from the terminal cannot re-enter the building, or any other adjacent building, through ventilators, windows, doors, other sources of natural air infiltration, or forced ventilation/air conditioning.
4.4 VENTILATION REQUIREMENTS The following notes are for general guidance: - It is not necessary to have a purpose provided air vent in the room or internal space in which the appliance is installed. - If the boiler is to be built into a small cupboard or compartment (i.e. at minimum clearances)and overheating can be forseen (i.e. close proximity to a cooking appliance etc) permanent air vents are recommended for cooling purposes in the cupboard or compartment .
- A heating by-pass should be fitted to ensure that the above condition is satisfied. If thermostatic radiator valves are to be installed, at least one radiator should be without a thermostatic valve (usually the bathroom radiator). - A sealed system must only be filled by a competent person using the approved method shown. - The following paragraphs outline the specifications of the items fitted to the boiler. Expansion vessel.
5.- INSTALLATION INSTRUCTIONS 5.1 BOILER PACKAGING The boilers are supplied in different packagings: - Boiler - 1m flue system (separate packaging) 5.2 FITTING THE BOILER. - Decide where the boiler is to be fixed on the wall taking into account the installation requirements detailed in section 4.2 and the clearances and dimensions described in the technical data. The centres for the hanging strap fixing are 85mm below the top of the boiler casing, see fig below.
5.3 WIRING INSTRUCTIONS Warning: observe the usual precautions to ensure that the electricity supply is isolated before commencing any installation or service work. - The appliance is fitted with a flying lead for 230 V ~ 50 Hz. This should be wired as described in section 4.5 electricity supply. Note: The ignition and flame control by ionisation circuit is polarised. For this reason, it important that live and neutral are not reversed.
5.5 AIR/FLUE SYSTEM The FEB20E boiler comes supplied with a Ø 60 - 100mm coaxial air/flue kit. The maximum length of the combustion and intake pipes which may be used with the FEB20E boiler is three meters, measured from the 90° bend. Each extra 90° bend or two 45° bends, reduces the available length by 0.8m. (See installation examples). It is recommendable to fit the pipe at a slight 2° or 3° downwards incline to prevent any water or condensation from entering in the boiler.
6.- COMMISSIONING INSTRUCTIONS Before commissioning the appliance, the whole gas installation including the meter MUST be purged and tested for gas soundness. IMPORTANT: open all doors and windows, extinguish naked lights, and DO NOT SMOKE whilst purging the gas line. Before commencing the commissioning procedure, ensure that the central heating system and the domestic hot and cold water system have been flushed. This will remove contamination which could cause the boiler to fail. 6.
6.5 INITIAL OPERATION CONTROL PANEL. 6 1.- Programmable timer 7 8 9 2.- Heating temperature and pressure gauge 3.- Central heating temperature selector 1 12 40 60 20 4.- Main control switch 9 3 80 100 0 120 0 4 6 3 bar 2 1 5.- D.H.W. temperature selector FEB-20E 6.- Green neon light (boiler ready) 7.- Orange neon light (burner functioning) 1 8.- Red neon light (boiler locked out) 2 3 5 4 6.5.
6.6 FINAL CHECKS - Re-light and test for gas soundness - Set the C.H. and D.H.W. temperature selectors to the required settings. - Ensure that the time clock and/or room stat (if fitted) are set to the required setting (s). 6.
7.2 BURNER AND HEAT EXCHANGER INSPECTION AND CLEANING The front of the sealed air box must first be removed (6 screws) and care should be taken to avoid damaging the seal. The combustion chamber cover can then be removed (4 screws) taking care not to damage the delicate insulation material inside. Inspect the burner and heat exchanger fins for debris and soot. Check also for rubbish below the burner. 7.
8.- WIRING DIAGRAMS 1 2 3 4 30 MP 25 26 27 1 24 2 FIL 28 J19 29 J5 J2 22 3 21 J1 20 P3 19 J10 J11 P2 17 J8 4 P1 16 S3 S4 S1 15 S2 J6 5 4 3 2 1 5 J12 J4 J9 14 8 7 13 6 12 11 10 1. Filter 2. Supply 3. Earth 4. Fan 5. Pump 6. Ignition 7. Burner solenoid valve 1 8. Burner solenoid valve 2 10. Flow switch 11. Air pressure switch 12. Room thermostat (optional) 13. Terminal block (Room thermostat) 14. Clock connection 15. Modulating Electro-valve 16.
SELF DIAGNOSTIC FAULT CODES The FEB-20E has a built in self diagnostic fault finding system incorporated into the P.C.B. Should a fault develop on the boiler which could cause a situation liable for the operation of the boiler to become unsafe, then the boiler will fail safe by locking-out which is displayed via the 'red neon' on the control panel. The fault can be identified by the different sequences in which the 'red neon' flashes and the duration that the neon stays illuminated.