User`s manual

CHAPTER 3.0 Wiring and Installation 3-27
CDS7324 (FORMERLY LSF-0819)
Rev. A INSTALLATION & USER’S MANUAL
3.7.1.4 Size D
EMC Filter,
Fuses etc.
See
Section 2
Installation
4 5 6
U1 V1 W1
Connector J9
D
3
PE
a.c. Mains
L1
L2
L3
Protective
Earth
Figure 3.20 Size D AC Mains Input Connection
- Fixed connector: 4 pole, screw terminal
- D size wiring: cable 6 AWG (13 mm
2
) for 50/140
- D size wiring: cable 4 AWG ( 21mm
2
) for 60/180
- PE Terminal wiring: cable 6 AWG (13 mm
2
) for 50/140
- PE Terminal wiring: cable 4 AWG (21 mm
2
) for 60/180
- Stripping Length 16mm
- Tightening Torque: 2-2.3Nm
Pos. Name Function
J9.3 PE Protective Earth Screw Terminal
J9.4 U1
Phase "L1", three-phase voltage input 230/460Vac ±10%
J9.5 V1
Phase "L2", ", three-phase voltage input 230/460Vac ±10%
J9.6 W1
Phase "L3", ", three-phase voltage input 230/460Vac ±10%
Table 3. -6 J9 AC Mains Power connector, D Size