User`s manual
CHAPTER 3.0 Wiring and Installation  3-27
CDS7324 (FORMERLY LSF-0819)   
Rev. A  INSTALLATION & USER’S MANUAL 
3.7.1.4 Size D 
EMC Filter, 
Fuses etc. 
See 
Section 2 
Installation
 4 5  6 
 U1  V1  W1 
Connector J9 
D
3 
PE 
a.c. Mains 
L1 
L2 
L3 
Protective 
Earth 
Figure 3.20 Size D AC Mains Input Connection 
-  Fixed connector: 4 pole, screw terminal 
-  D size wiring: cable 6 AWG (13 mm
2
) for 50/140 
-  D size wiring: cable 4 AWG ( 21mm
2
) for 60/180 
-  PE Terminal wiring: cable 6 AWG (13 mm
2
) for 50/140 
-  PE Terminal wiring: cable 4 AWG (21 mm
2
) for 60/180 
-  Stripping Length 16mm 
-  Tightening Torque: 2-2.3Nm 
Pos. Name  Function 
J9.3  PE  Protective Earth Screw Terminal 
J9.4  U1 
Phase "L1", three-phase voltage input 230/460Vac ±10% 
J9.5 V1 
Phase "L2", ", three-phase voltage input 230/460Vac ±10% 
J9.6 W1 
Phase "L3", ", three-phase voltage input 230/460Vac ±10% 
Table 3. -6 J9 AC Mains Power connector, D Size 










