CHAPTER 3.0 Wiring and Installation  3-14
CDS7324 (FORMERLY LSF-0819)   
Rev. A  INSTALLATION & USER’S MANUAL 
3.2.1  CE Items for Mechanical Installation 
Additional electromagnetic compatibility (EMC) measures must be installed on 
equipment associated with the DS2110 Servo-drive. The following measures must be 
implemented: 
•  All external Regen (Regenerative circuit) resistors used with the DS2110 must 
be installed in enclosures which provide a degree of ingress protection against 
liquids and objects of at least IP22 and which are accessible to technically 
qualified service or maintenance persons only. Protection against electric shock 
must be maintained when installing these resistors. 
•  Use shielded cable to connect the external regen resistor (if installed) to the 
DS2110 power supply. The length of this cable should be as short as possible. 
The shields of these cables should be earthed to Chassis Earth using the 
optional EMC Bracket kit or the panel earth bar. Alternatively, if the cable is 
required to pass through an enclosure panel earthed to Chassis Earth, the shield 
may be earthed to the panel by use of a 360 degree metal cable gland. 
•  Cables supplying external d.c. supply voltages to the DS2110 Series Servo-
drives (for example, the 24 Vd.c. supply) must be as short as possible. The 
supply wires should be twisted together or alternatively shielded cable should be 
used. 
•  Cables connecting the D.C. Bus from the DS2110 Power Supply to other 
DS2110 Servo-drives must be as short as possible. The supply cables should be 
shielded. 
•  Motor power cables must be shielded with the cable shield securely connected 
to Chassis Earth at both ends of the cable. At the DS2110 Servo-drive end of the 
cable, the shield should be earthed using the EMC Bracket. 
•  Motor feedback & signal cables must be shielded with the cable shield securely 
connected to Chassis Earth at both ends of the cable. 
•  Signal cables must be shielded with the cable shield securely connected to make 
a good HF earth bond to Chassis Earth at both ends of the cable. 
Further details for the correct installation and shielding of cables and conductors are 
given in Chapter 2. 
Required for 
CE-Compliance
CAUTION - Enclosure or cabinet temperature control is critical for performance, 
reliability and life of electrical components. Maintaining a uniform temperature (check 
for hot spots) within the specified values for the equipment will prevent premature 
failure due to temperature stress. 