5.12.4 Fault Clearing 
It is possible to clear all faults except for those faults that occur during the initialization process and faults due to 
microprocessor exceptions. It is possible to determine whether one of these non-clearable faults has occurred by 
reading the status_controller
 parameter (1522). If bit 6 of this parameter is 1, then a non-clearable fault has 
occurred. (where bit 0 is LSB). 
To clear faults, the parameter errors_clear
 (1491) must be written with a value of 1. 
The actions performed when clearing errors are as follows: 
1.  real-time fault monitoring is disabled 
2.  fault flags, latched faults and fault counters cleared 
3.  non-fault state requested in drive state machine 
4.  when non-fault state achieved then errors_clear is reset to 0 
5.  real-time fault monitoring re-enabled 
The completion of the fault clearing process can be verified by reading errors_clear. Once the process has 
completed the fault monitoring operates normally and so if a fault is still present it will be detected again. 
5.12.5 Event Log 
The DS2110 maintains a non-volatile log of faults and status to aid fault diagnosis. The event log contains the last 
850 (approx.) faults that occurred on the drive and is a circular buffer. The data recorded for each fault entry in the 
event log is as follows: 
Field 
Number 
Type Name  Description 
1499 U32 event_log_timesta
mp 
total power on time in seconds as a 32-bit unsigned integer 
1500 U32 event_log_data1  top 16 bits: status code defining event logged 
next 8 bits: 1=status set, 2=status cleared 
low 8 bits: ambient temperature as 8-bit signed integer 
1501 U32 event_log_data2  additional event information 
Table 5.44 Event log data parameters 
When retrieving event log information, there are some additional parameters that give information on how many 
events have been logged and allow the user to retrieve the required part of the event log. These parameters are 
described in the table below: 
Field 
Number 
Type Name  Description 
1494 U32 event_log_size  number of bytes used in event log since last power on 
1640 U32 event_log_increment  number of bytes used per entry in event log (currently 12) 
1495 U16 event_log_current_positio
n 
byte pointer to current position in event log 
1498 U16 event_log_read_pointer  byte pointer to position to read from in event log 
Table 5.45 Error log access parameters 
WARNING:- DELAY IN RE-DETECTING FAULTS 
After the DS2110 has cleared faults, the time taken to redetect a particular fault depends upon the rate at 
which it is monitored. Typically, parameters that only change slowly under normal circumstances (such as 
temperatures) may only be monitored every 100ms. 
Therefore, a delay of 0.5s should normally be allowed after clearing faults before re-enabling the drive 