CHAPTER 4.0 Getting Started 4-6
CDS7324 (FORMERLY LSF-0819)
Rev. A INSTALLATION & USER’S MANUAL
4.7 Regen Resistor Configuration
µA size and select A and B size DS2110 are equipped with an internal regeneration resistor. All other A to E size
drives will require an external resistor to be attached. The recommended regeneration resistors are detailed in
Section 5.3.5.
The Regen-on/ Regen-off voltages should be set in accordance with the DC Bus voltage, Table 5.4 Typical
Regeneration Turn-on & Turn-off Voltage Levels. These parameters are automatically set when the motor
parameters are downloaded to the controller but should be verified to ensure safe operation.
Open DS2110
Drive Setup
Regen Resistor
Regen Parameters” and ensure that the “Regen-On
Voltage (V)” and “Regen-Off Voltage (V)” are set correctly
Select Read All.
Confirm that values are correct.
Figure 4.5 Regeneration Parameters