CT Corsair   Final Report   May 2, 2014 
25 
 Figure 25. Model Setup Window for Model Selection 
Rotational Actuator (Actual) 
Linear Actuator (Same Parameters) 
G405-1034A 
G415-800A PTC 
 Table 6. Actuator Model Numbers 
After the motor model is selected, the software parameters could then be set and adjusted using 
its internal menus which include System Setup, I/O Setup, and Motion. By default, the actuator 
was then launched in Commissioning Mode. This mode limits output speed and torque to 10% of 
the possible  maximum. By entering  the  Diagnostics  Window,  this  percentage was  adjusted to 
20%. It is here that the PIV gains of the controller were tuned and other parameters including 
fault time outs were modified. See Figure 26 for these values. 
Figure 26. Diagnostics Setup Window 