User`s manual
SECTION 2: SAFETY & EMC INSTRUCTIONS
DS2100 User's Manual
C27750-001 PAGE 2-27
• Motor Overload Protection: The DS2100 does not incorporate an internal motor load protection. The drive is
intended to be used with motors that have integral thermal protection in the form of an NTC or PTC thermistor. The
selections of NTC or PTC and overtemperature fault level are set in software. See ‘Motor Thermal Parameters’ and
‘Motor Thermal Protection Mechanism’ in Section 5 of this manual.
• Overcurrent Protection: The DS2100 is equipped with internal over current protection. See the ‘Cabling and
Interconnect Protection Scheme’ detailed in Section 5 of this manual.
• The Integral Motor Thermal Protection signal shall be connected on the equipment, on G361 connectors
J4/J5 (PIN 8-15/6-8), which accepts signals maximum 5.5 Vdc ±10%, 400 µA. The ultimate result of this signal is
to "Switch-OFF" the output of the Solid State Motor Controller and thereby "No-Power" is transmitted to the Motor
connected to the Motor-Drive.