User`s manual

SECTION 2: SAFETY & EMC INSTRUCTIONS
DS2100 User's Manual
C27750-001 PAGE 2-7
DS2100 Models
Size µ
µµ
µA
Size 3/11 6/22
Notes
Short Circuit Rating 5,000 Amps
rms
Power Line Fuse 25A, 660V FWP25-A1F Semiconductor
(Cooper Bussmann)
Recovery Resistor Fuse
Contact Moog Application Engineering for Advice
24Vdc Auxiliary
Power Supply Fuse
3A, 250V Delayed
DS2100 Models
Size A Size B
Size 8/22 14/42
Notes
Short Circuit Rating 5,000 Amps
rms
Power Line Fuse
50-FE 690V Semiconductor
(Cooper Bussmann)
Recovery Resistor Fuse
Contact Moog Application Engineering for Advice
24Vdc Auxiliary
Power Supply Fuse
3A, 250V Delayed
DS2100 Models
Size C Size D
Notes
Size 20/45 25/70 30/90 50/140 60/180
Short Circuit Rating 5,000 Amps
rms
10,000 Amps
rms
Power Line Fuse 100-FE 690V 160-FEE 690V Semiconductor
(Cooper Bussmann)
Recovery Resistor Fuse
Contact Moog Application Engineering for Advice
24Vdc Auxiliary
Power Supply Fuse
3A, 250V Delayed
DS2100 Models
Size E
Notes
Size 100/300
Short Circuit Rating 10,000 Amps
rms
Power Line Fuse 315-FM Semiconductor
(Cooper Bussmann)
Recovery Resistor Fuse
Contact Moog Application Engineering for Advice
24Vdc Auxiliary
Power Supply Fuse
3A, 250V Delayed
Table 2.1 Recommended DS2100 Fusing
WARNING
In the event of a fuse failure, remove all power, refrain from working on the
unit for at least 5minutes for the µA size (6 minutes for the A-E sizes) to allow all internal
voltages to decay to a safe level. Remove all fuses from the system. Determine the source
of the failure before re-commencing operation of the drive.