User`s manual
DS2100 User's Manual SECTION 5: DS2100 FUNCTIONAL OVERVIEW
PAGE 5-10 C27750-001
The parameters associated with the regeneration control are given below.:
Parameter Name Index / Subindex Description
regen_enable 0x24A4 / 21 Regeneration Control Mode
0 - Regeneration Off
1 - Duty cycle controlled
2 - Duty cycle controlled + power fault
3 - Power fault only
4 - Power warning only
regen_on_voltage 0x24A4 / 2 Regeneration Transistor Turn-on Voltage
regen_off_voltage 0x24A4 / 1 Regeneration Transistor Turn-off Voltage
regen_power_filtered 0x24A4 / 5 Average Regeneration Power (Measured)
regen_internal_resistance 0x24A4 / 11 Internal Regeneration Resistor Resistance
regen_internal_resistor_power 0x24A4 / 12 Internal Regeneration Resistor Power
regen_internal_resistor
initial_on_time
0x24A4 / 14 Internal Regeneration Resistor Initial on-time in ms
regen_internal_resistor_contin
uous_on_time
0x24A4 / 13 Internal Regeneration Resistor Continuous on-time in ms
regen_external_resistance 0x24A4 / 15 External Regeneration Resistor Resistance
regen_external_resistor_power 0x24A4 / 16 External Regeneration Resistor Power
regen_external_resistor_initial
_on_time
0x24A4 / 18 External Regeneration Resistor Initial on-time in ms
regen_external_resistor_contin
uous_on_time
0x24A4 / 17 External Regeneration Resistor Continuous on-time in
ms
regen_power_capability 0x24A4 / 22 Total Regeneration Power Capability
regen_max_current 0x24A4 / 19 Maximum Regeneration Current
Table 5.3 Regeneration Parameters
The Regeneration transistor turn-on and turn-off voltages are set with the motor parameters and DC bus overvoltage
level. Typically these voltages are set at follows.
Motor Voltage Bus Overvoltage Regen on Voltage Regen off Voltage
300V 400V 390V 380V
600V 800V 780V 760V
Table 5.4 Typical Regeneration Turn-on & Turn-off Voltage Levels
For drives equipped with an internal Regeneration resistor, the parameters associated with that resistor are set
automatically. If the drive has external regeneration capability only, all regeneration resistor parameters are set to
zero by default. In this case, the drive will display a fault (F3) and will not enable until suitable parameters for the
external regeneration resistors are entered and saved.
The software also checks the value of regeneration resistance entered. If too low a value is entered, such that the
current that would flow on turn-on of the regeneration transistor exceeds the ratings of the regeneration, transistor, a
fault (F3) is also reported.