SECTION 4: GETTING STARTED
PAGE 4-8 C27750-001
4.7 Regen Resistor Configuration
Only the µA size DS2100 is equipped with an internal regeneration resistor. The larger sizes (A-D) require an external
resistor to be attached. The recommended regeneration resistors are detailed in Section 5.3.5.
The Regen-on/ Regen-off voltages should be set in accordance with the DC Bus voltage, Table 5.4 Typical Regeneration
Turn-on & Turn-off Voltage Levels. These parameters are automatically set when the motor parameters are downloaded
to the controller but should be verified to ensure safe operation.
Open “DS2100
Drive Setup
Regen Resistor
Regen Parameters” and ensure that the “Regen-On Voltage
(V)” and “Regen-Off Voltage (V)” are set correctly
Select Write All.
Confirm that values are correct.
Figure 4.8 Regeneration Parameters