R520-ST & R620-ST Power Vent Indoor Gas Fireplace
Part No. XG0773 - 032211
b bl
h
d
Installation
NOTE: Remember, both sides of the Fireplace require the same quantities of wood, drywall and hardware.
Cut the Upper and Lower Horizontal 2 x 4's as shown in Figure 2b. Next, cut the Required quantity of short ller 2x4's under the lower Horizon-
tal. Follow Typical building codes and practices when spacing. Next, cut the Required Left and Right Vertical 2 x 4's as shown in Figure 2b.
Lastly, install the Two (2) Supplied Steel Headers above the replace throat positioned to attach facing material.
NOTE: When this assembly is in place, ensure ALL the required clearances to combustibles are maintained.
Figure 2b. Fireplace installation, Both Sides are Typical.
Step 4. Installation of the RHS 102 heat shield
When the vent passes through the rst adjacent ceiling (or wall for horizontal runs) a Montigo RHS102 heat shield must be installed around the
pipe as shown above.
See the detail of the RHS 102 on the following page.
1” clearance
1” clearance
Non-Com usti e ea er
(supplied by Montigo)
2-pcs 2 x 4 (vertical)
Both Sides Typ
2 x 4, (Top
horizontal)
2 x 4, (Bottom
horizontal)
Both
Sides
Typ
(vertical)
use Typical
building
practices
when
spacing.
RHS 102
Distance between 2 x 4's
R520 = 71½"
R620 = 83½"