Specifications

XG0201 Rev. 02 03/2001
Page 8
M38DV-ST / ME38DV-ST Direct Vented Fireplace
InstallationInstallation
InstallationInstallation
Installation
Installation Of Vertical Vent DV
n Vertical Terminations must be installed:
minimum 2' (two feet) above the highest point where
vent passes through the roof.
minimum 6' (six feet) from a mechanical air inlet
minimum 18" (1 1/2 feet) from a parapet wall.
n Maximum vent height is 30 feet above fireplace.
Note: Flame characteristics will change if the maximum vent height
is used.
n Minimum clearances 2" from vent to all combustible materials must
be maintained.
n A maximum of two offsets (each offset has two 90° bends) may be
made if the length of the offsets does not exceed 25% of the vertical vent
height, when measured center to center of piping.
Example: Typical vent installation.
30' vertical vent
2 - 2' offsets required
25% of 30' = 7-1/2' max. offset allowed
This venting configuration meets requirements.
A - Termination PVTK-1
B - Flex sections PFL-1 (12" section)
PFL-2 (24" section)
PFL-3 (36" section)
PFL-4 (48" section)
C - Solid sections PEXT-1 (12" section)
PEXT-2 (24" section)
PEXT-3 (36" section)
PEXT-4 (48" section)
D - Support Ring & Plate PSPXT-7 (8" dia.)
E - Firestop PS-8 (8" dia.)
F - Roof Flashing PRF-7 (1/12 - 7/12 pitch)
PRF-12 (7/12 - 12/12 pt.)
Figure 13b. Vertical venting with 2 offsets (1 offset= two 90° bends).
Figure 13a. Vertical venting with 1 offset (1 offset= two 90° bends).
Storm collar
Support ring
MEXT
Solid Section
Roof flashing
30' max.
Support plate
Firestop
Firestop
2' min.
MXT-10
Adaptor
MEXT
Flue
Collar
Figure 12. Straight, vertical venting using
required PXT-10 adaptor.
2' min.
2'
Storm collar
Roof flashing
30' max.
Support straps or
support plate & ring
Firestop
Firestop
Firestop
Support plate
& ring
2' min.
Storm collar
Support ring
Roof flashing
30' max.
Support plate
Firestop
* Minimum 1" clearance to combustibles, on vertical vent runs.
* Minimum 1" clearance to combustibles, on vertical vent runs.
* Minimum 1" clearance to combustibles, on vertical vent runs.
PEXT
PEXT
PXT-10