Specifications

22

Only For Qualied Installers
Natural Gas or Propane
 
 
 
  
 

A vent damper is provided to allow ne tuning
of the draft. Too little draft will cause ames to be too
long with black tips and too much draft will cause
ames to be short and blue.
To adjust the damper, burn the unit on High 10
minutes or more. Adjust the vent damper to a posi-
tion in the ranges listed below that produces the most
desirable ame pattern.

Top Vent Only
Vent damper shown in the
Maximum Draft”OPEN” position
for top vent. Note: This would be
the Minimum Draft”CLOSED”
position if a rear vent was
installed.
OPEN
CLOSED
ONE HALF