Specifications

G0204
Page 4
Panorama Direct Vented Fireplace
Installing The Gas Line
The gas line must be installed before finishing the M38DV-PRC
fireplace. Natural Gas requires a minimum inlet gas supply pressure of
5.5" W.C. & a manifold pressure of 3.5" W.C. Propane Gas requires a
minimum inlet gas supply pressure of 11" W.C. & a manifold pressure
of 10" W.C. Provision must also be made for a 1/8" N.P.T. plugged
tapping and be accessible for test gauge connection immediately
upstream of the gas supply controls to the appliance. The fireplace gas
connection and the main operating gas valve is located behind the
removable brass trim at the bottom of the unit and need only be
attached to the gas line with an approved fitting, as required by the
applicable installation codes.
* After gas line is connected each appliance connection,
valve and valve train must be checked while under normal
operating pressure with either a liquid solution, or leak
detection device, to locate any source of leak. Tighten any
areas where bubbling appears or leak is detected until
bubbling stops completely or leak is no longer detected. Do
NOT use a flame of any kind to test for leaks.
Figure 4. Gas line access.
The appliance and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing of that
system at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system by
closing its individual manual shutoff valve during any pressure testing of
the gas supply piping system at test pressures equal to or less than 1/2
psig (3.5 kPa).
Installation
Vent Installation
This section covers the installation of direct venting and terminations.
For a detailed diagram of allowed termination locations, see Appendix
A.
Installation Requirements
n The M38DV-PRC fireplace uses Premium venting components
with:
5" inner dia. /8" outer dia.
n Minimum 2" clearance to combustibles required for vent pipes
n Use only certified Montigo vent components. (Use of other parts will
void the Montigo warranty, and may impede the operation of the
fireplace.)
n All joints must be secured with a minimum of two screws per joint
n Vent terminations must not be recessed in walls or siding
n Horizontal runs must be supported by a minimum of two supports
per horizontal run. A minimum of one screw on each side of
support is also required
n Flex vent sections may be stretched up to 50% of their total length
(eg. a 24" section may be stretched to 36")
n Maximum horizontal run for a flex section with no vertical rise is 3 feet.
n Flex vent sections over 3 feet must fall within the limits set by the
venting graph and must have a minimum vertical rise of 3 inches
per foot of flex.
n Venting components can be used in any combination of solid/rigid
n Solid vent sections may be cut less than half way from the tapered end
n Venting components can be used in any combination of solid/rigid
pipe or flex pipe and in any orientation (Male connectors can face
in any direction)
Vent terminations can be very hot. National Standards
require that all terminations accessible to the public (below 7
feet from grade level, on balconies, or decks) be installed
with a certified Montigo Heat Guard. (Part no. PTKOG)
Do not obstruct, or attempt to conceal, the vent termination.
These actions will affect the operation of the fireplace, and
may be hazardous.
In heavy snow areas, take extra care to prevent snow
buildup from obstructing the vent termination.
CAUTIONS:
Installing The Remote Switch
The M38DV-PRC is equipped with a remote-operated valve for use
with a wall switch. See Figure 19 for information on wiring the switch.
The valve is pre-wired and generates its own power. DO NOT connect
any external power to it.
Note: The switch location must not exceed 30' from the fireplace.