Owner`s manual

Page 9
L52DF Flush Indoor Gas Fireplace
Part No. XG0185 - 092909
f i r e f e a t u r e
Installation
Figure 12. Extended Installation using a combination of solid and ex
venting. Use the vent graph to determine your allowable
run, then select appropriate components.
Example 2:
Rigidsectionsandanelbowusedinconjunctionwith3ft.exsection
(PFL-3)will,whenextendedinavefootchase,allowforamaximum
horizontalrunoftwelveandone-halffeetfromthecentreofthereplace
to outside wall and a minimum of 7'6" when retracted in opposite direction
(see Figure 12 and 13).
"C"exsectionsand"D"rigidsectionsmaybeusedinconjunctionwith
one another to obtain different possible horizontal length installations.
NOTE: Flex section with no vertical rise must not exceed maximum
horizontal length of 3 feet (see Figure 14). Flex runs over 3 feet must
fall within the limits set by the venting graph, and must have a minimum
verticalriseof3"perfootofex.
Figure 13. Retracted Installation using a combination of solid and ex
venting. Use the vent graph to determine your allowable
run, then select appropriate components.
Figure 14. Horizontal ex installation with MIN vertical rise.
B. Vertical (Through-The-Roof) Installations
5/8" with option for 4/7" (on applicable models)
Vertical rise >12' can be reduced (on applicable models).
Vertical Terminations must be installed:
minimum 2' (two feet) above the highest point where
vent passes through the roof.
minimum 6' (six feet) from a mechanical air inlet
minimum 18" (1 1/2 feet) from a parapet wall.
Maximum vent height is:
• 35feetabovereplace.
Note: Flame characteristics will change if the maximum vent height
is used.
Minimum clearances 2" from vent to all combustible materials must
be maintained.
A maximum of two offsets (each offset has two 90° bends) may be
made and shall not exceed total length of 25% of the vertical vent
4’ max.
RHS 8,
4’
vent run or
less, use RHS101
Example: Typical vent installation.
20' vertical vent
5" / 8" Venting
A - Termination PVTK-1
B - Flex Sections PFL-1 (12" Section)
PFL-2 (24" Section)
PFL-3 (36" Section)
PFL-4 (48" Section)
C - Rigid Sections PEXT-1 (12" m/f Section)
PEXT-2 (24" m/f Section)
PEXT-3 (36" m/f Section)
PEXT-4 (48" m/f Section)
D - Support Ring
& Plate
PSPXT-8
E - Firestop PS-8
F - Roof Flashing PRF-7 (1/12 - 7/12 pt.)
PRF-7 (7/12 - 12/12 pt.)
G - Adaptor / Vent
Reducer
PVA5487 (5"/8" to 4"/7")