Owner`s manual

Page 10
L42DF-ST See-thru Indoor Gas Fireplace
Part No. XG0812 - 081009
f i r e f e a t u r e
Installation
Vertical Vent Installations
Vertical vent Installations.
minimum 2' (two feet) above the highest point where
vent passes through the roof.
minimum 6' (six feet) from a mechanical air inlet
minimum 18" (1 1/2 feet) from a parapet wall.
Maximumventheightis32feetabovereplace.
Note: Flame characteristics will change if the maximum vent
height is used.
Minimum clearance to combustible construction around the
vent pipe is 1" on all sides must be maintained, except on hori-
zontal venting where the top of the pipe must have a clearance of
at least 2".
2. Offset Vertical Installations
A maximum oftwo offsets (each offset has two 90° bends) may be
made if the length of the offsets does not exceed 25% of the vertical
vent height, when measured center to center of piping.
Example: Typical vent installation.
32' vertical vent
2 - 2' offsets required
25% of 30' = 7-1/2' max. offset allowed
This venting configuration meets requirements.
1. Straight Vertical Installation
Figure 17. Straight, vertical venting run.
Figure 17b. Vertical venting with 2 osets (1 oset= two 90° bends).
Figure 17a. Vertical venting with 1 oset (1 oset= two 90° bends).