Owner`s manual
L42DF-ST* Indoor Gas Fireplace
XG0182 - 112811
Installation
The maximum termination point is 32’ above the replace (NOTE:
if the maximum termination height is used, the ame pattern
may be affected).
The Vertical termination must be a minimum 2’ higher than where
the termination exits the roong materials, (asphault shingles,
cedar shakes, etc). This distance should be measured from the
high side of the roof slope where the ue ashing intersects the
roong materials. (see Figures 11 to 11c *).
Termination location must be a minimum 6’ from a mechanical
air inlet.
Termination location must be a minimum 18” from a parapet wall.
A maximum of two offsets (each offset is made up of 2-90°
bends) may be made.
Install a restop at any location where venting passes through
combustible materials and construction.
Utilize support straps, or support plates, and rings (as required)
to meet acceptable building practices.
Install all roof ashing and storm collars as shown.
. Top vent, Roof mounted termination with no offset in vent run.
Top vent, Roof mounted with 1 offset (1 offset= two 90° bends).
Top vent, Roof mounted with 2 offsets (1 offset= two 90° bends).
The following details are some possible congurations for Roof
mounted terminations. See below.
PVTK1 Termination
PVTK1 Termination
PVTK1 Termination