Owner`s manual


L42DF-ST* Indoor Gas Fireplace
XG0182 - 112811
Installation
 



 


The maximum termination point is 32’ above the replace (NOTE:
if the maximum termination height is used, the ame pattern
may be affected).
The Vertical termination must be a minimum 2’ higher than where
the termination exits the roong materials, (asphault shingles,
cedar shakes, etc). This distance should be measured from the
high side of the roof slope where the ue ashing intersects the
roong materials. (see Figures 11 to 11c *).
Termination location must be a minimum 6’ from a mechanical
air inlet.
Termination location must be a minimum 18” from a parapet wall.
A maximum of two offsets (each offset is made up of 2-90°
bends) may be made.
Install a restop at any location where venting passes through
combustible materials and construction.
Utilize support straps, or support plates, and rings (as required)
to meet acceptable building practices.
Install all roof ashing and storm collars as shown.
. Top vent, Roof mounted termination with no offset in vent run.
 Top vent, Roof mounted with 1 offset (1 offset= two 90° bends).
 Top vent, Roof mounted with 2 offsets (1 offset= two 90° bends).

The following details are some possible congurations for Roof
mounted terminations. See below.
PVTK1 Termination
PVTK1 Termination
PVTK1 Termination