Owner`s manual


L42DF-ST* Indoor Gas Fireplace
XG0182 - 112811
Installation

1). Frame in the enclosure for the unit with framing materials. The
framed opening for the assembled replace is 45" wide, x 40" high
x 23 3/4" deep, see Figure 2
.
       

Figure 22
Framing dimensions.

When installing a shelf over the top of the replaces, the following
guidelines must be adhered to:
For Rear Vent applications, the minimum clearance is 2" from the rear of
the replace to a wall, or any combustible materials, and 12" clearance
from the top of the replace to the underside of any combutible shelf
materials.
For Top Vent applications, the minimum clearance is 2" from the rear
of the replace to a wall, or any combustible materials, and 17" (LP) &
12"(NG) to the underside of any combutible shelf materials.
(Minimum 2" clearance must still be maintained around the vent
pipes.)
 Framing dimensions, (Back-framing)
 Combustible Framing for shelves over the replace, Top vent.
 Combustible Framing for shelves over the replace, Side vent.
 Non Combustible Framing with alcove above replace,
Right side. Combustible Framing above replace, Left side, see
gure 2. (Top Vent).
MODEL
Top-Rear Vent
Top-Top Vent
(NG)
Top-Top Vent
(LP)
Back
Sides
Floor
Mantel
       
Notes:
Install supplied metal headers (Part No.
H42ST060) above replace after unit is in
place.
Use supplied hardware to attach to framing.
Both Walls Typical. May not be exactly as
shown.
Framing Kit, 4-pcs. (Part No. L42FS01B)
Install with supplied hardware. Both
walls and sides Typical. See Figure 2a
below.
40”
45”
23 3/4”
40”
36”
Both walls Typical. May
not be exactly as shown.
Backframe Min. 42”
both sides Typical
Combustible materials may be used,
(left & right), surround & bottom.
Above fireplace see Fig. 24 & 25.
Framing Kit, (Part No. L42FS01B,
4-pcs. Fasten to Combustible
framing with supplied hardware.
12” Min.
Combustible
shelf
Supplied shield
90°
1” Min.
1” Min.
L.P. & N.G
12” Max.
4
1”Min N.G.
54”Min L.P.
12” (NG)
17” (LP)
Min.
PEL Short
90 elbow
Supplied shield
Combustible Shelf
N.G. & L.P
2” Min.
Non
Combustible
Header
7”
Floor
Alcove over
Fireplace Non
-
Combustible
Materials Only
36”
30 1/2”
door
opening
40”
7”
Combustible
Header
Min. 1”
Supplied
Header
10”
Top vent
N.G. & L.P
95” Min.