Owner`s manual
L42DF-ST* Indoor Gas Fireplace
XG0182 - 112811
Installation
1). Frame in the enclosure for the unit with framing materials. The
framed opening for the assembled replace is 45" wide, x 40" high
x 23 3/4" deep, see Figure 2
.
Figure 22
Framing dimensions.
When installing a shelf over the top of the replaces, the following
guidelines must be adhered to:
For Rear Vent applications, the minimum clearance is 2" from the rear of
the replace to a wall, or any combustible materials, and 12" clearance
from the top of the replace to the underside of any combutible shelf
materials.
For Top Vent applications, the minimum clearance is 2" from the rear
of the replace to a wall, or any combustible materials, and 17" (LP) &
12"(NG) to the underside of any combutible shelf materials.
(Minimum 2" clearance must still be maintained around the vent
pipes.)
Framing dimensions, (Back-framing)
Combustible Framing for shelves over the replace, Top vent.
Combustible Framing for shelves over the replace, Side vent.
Non Combustible Framing with alcove above replace,
Right side. Combustible Framing above replace, Left side, see
gure 2. (Top Vent).
MODEL
Top-Rear Vent
Top-Top Vent
(NG)
Top-Top Vent
(LP)
Back
Sides
Floor
Mantel
Notes:
Install supplied metal headers (Part No.
H42ST060) above replace after unit is in
place.
Use supplied hardware to attach to framing.
Both Walls Typical. May not be exactly as
shown.
Framing Kit, 4-pcs. (Part No. L42FS01B)
Install with supplied hardware. Both
walls and sides Typical. See Figure 2a
below.
40”
45”
23 3/4”
40”
36”
Both walls Typical. May
not be exactly as shown.
Backframe Min. 42”
both sides Typical
Combustible materials may be used,
(left & right), surround & bottom.
Above fireplace see Fig. 24 & 25.
Framing Kit, (Part No. L42FS01B,
4-pcs. Fasten to Combustible
framing with supplied hardware.
12” Min.
Combustible
shelf
Supplied shield
90°
1” Min.
1” Min.
L.P. & N.G
12” Max.
4
1”Min N.G.
54”Min L.P.
12” (NG)
17” (LP)
Min.
PEL Short
90 elbow
Supplied shield
Combustible Shelf
N.G. & L.P
2” Min.
Non
Combustible
Header
7”
Floor
Alcove over
Fireplace Non
-
Combustible
Materials Only
36”
30 1/2”
door
opening
40”
7”
Combustible
Header
Min. 1”
Supplied
Header
10”
Top vent
N.G. & L.P
95” Min.