Owner`s manual


L42DF* Indoor Gas Fireplace
XG0181 - 112811.1
Installation


The RHS8 Heat shield  be used when the Termination is 
() from the replace, or directly
off the rear of the replace, as shown gure 17a. The RHS101 Heat
Shield (Figure 18c and 18a)  be used within the noted dimensions.
To install the RHS8, frame an opening in combustible construction,
Figure 17 below. Slide the Heat shield in place over the vent pipe
which attaches to the replace. After the replace and vent pipe has
been installed, clearances should match the dimensions in Figure 17.
RHS8 Installation. (Install by sliding over vent pipe
where it passes through the combustible construction).
  RHS101 Installation. (Install by sliding Outer
Section over vent pipe where it passes through the
combustible construction.
 Heat Shield. After sliding the outer section in
place.

The RHS101 Heat shield  be used where the RHS8 Termination
(Figure 17 and 17a)  be used. Use the RHS101 where any
of the dimensions are within the parameters shown, gure 17a.
To install the RHS101, Slide the Inner Section over the vent pipe that
will connect to the replace. Then fasten the vent pipe to the back of the
replace with a minimum of three sheet metal screws. From the outside
slide the RHS101 outer section on see Figure 18. To complete the
installation fasten the Heat Shield Outer Section & Termination frame
to the structure Figure 18a.
RHS8 Installation. (Minimum requirements).
.
RHS101 Installation.
Termination
Drywall / sheetrock
RHS101 Heat Shield, inner Section
RHS101 Heat Shield
Outer Section
Combustible
framing
Termination
Drywall / sheetrock
RHS101 Heat Shield, inner Section
RHS101 Heat Shield
Outer Section
Vent pipe, from fireplace
RHS8 Heat Shield
1” Min. Both sides Typical
1” Min.
1” Min.
Combustible Framing
RHS8 Heat
Shield
36” Min
60” Min.
PTO Termination
Outer Shield 10 1/4”
3/8” Min. Both sides Typical
3/8” Min.
3/8” Min
.
Combustible Framing
Inner Shield 9 3/8”