Owner`s manual


L42DF* Indoor Gas Fireplace
XG0181 - 112811.1
Installation
 Rear Vent Venting Graph for wall mounted terminations.
 Rear Vented, wall mounted Multi-elbow termination
installation. Installation for L42DF* must have a minimum vertical
rise of 50".The vent run must comply with the Venting Graph for
Rear vent, wall mounted terminations, Figure 16.
. Straight run, Rear Vented, wall mounted termination
for L42DF*, Figure 16.

All dimension lengths for vertical or horizontal runs are measured
from center of the vent pipe.
Venting runs must fall within the limits set by the venting graphs,
see.
Fireplace must be converted to Rear Vent conguration prior to
running vent, see  and .

Measure the vertical height from the replace hearth to the centre of the
termination and the horizontal run from the replace ue collar to the wall
ange of the termination. Plot on the Venting Graph  with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.

If the vertical dimension from the hearth is 120" and the horizontal
run to the wall ange of the vent termination is 138", this would be an
acceptable installation.

If the vertical dimension from the hearth is 48" and the horizontal run
to the wall ange of the vent termination is 96", 


If the vertical dimension from the oor of the replace is 72" and the
horizontal run to the wall ange of the vent termination is 120", 

36” Max.
50” Min.
12”
Max.
Flex or Rigid
Section
23 3/8”
Min.
26 5/8”
26 5/8”
PXT Extension
RHS101 Heat
Shield
Termination
Hearth
Exterior
Wall
NOTE:
12” MAX. horizontal run with no vertical lift,
N.G. ONLY.
12” MAX.
36” Max.
50” Min.
12”
Max.
Flex or Rigid
Section
23 3/8”
Min.
26 5/8”
26 5/8”
PXT Extension
RHS101 Heat
Shield
Termination
Hearth
Exterior
Wall
NOTE:
12” MAX. horizontal run with no vertical lift,
N.G. ONLY.
12” MAX.
26 5/8”
12” N.G. ONLY
A
B
C
50”
48”
Unacceptable vent run
within shaded area.
Acceptable vent run
within non-shaded area.
If your installation does not fall within
the venting parameters, contact a
local Montigo dealer for Power
Venting options.
An inspection of the explosion relief flappers and door  be made prior to
lighting the fireplace. Faulty seal on the door gasket and/or explosion ports will
result in combustion products leaking into the living space and may result in
carbon monoxide poisoning.
