Owner`s manual


L42DF* Indoor Gas Fireplace
XG0181 - 112811.1
Installation
. Top vent, Roof mounted termination with no offset in vent run.
 Top vent, Roof mounted with 1 offset (1 offset= two 90°
bends).
 Top vent, Roof mounted with 2 offsets (1 offset= two 90°
bends).

The following details are some possible congurations for Roof mounted
terminations.
Support ring
Support plate
Firestop
32’ max.
2’ min.
PVTK1
Termination
Support ring
Support plate
Firestop
32’ max.
2’ min.
Obstacle
PVTK1
Termination
        




         

The maximum termination point is 32’ above the replace (NOTE:
if the maximum termination height is used, the ame pattern
may be affected).
The Vertical termination must be a minimum 2’ higher than where
the termination exits the roong materials, (asphalt shingles,
cedar shakes, etc). This distance should be measured from the
high side of the roof slope where the ue ashing intersects the
roong materials. (see Figures 11 to 11c).
Termination location must be a minimum 6’ from a mechanical
air inlet.
Termination location must be a minimum 18” from a parapet wall
For a more detailed diagram of allowed termination locations,
see . .
A maximum of two offsets (each offset is made up of 2-90°
bends) may be made.
Firestops must be installed as required by National & local codes.
Ensure all runs are supported with a minimum of 3 supports
per 10’ of venting.
Install all roof ashing and storm collars as shown.
PEXT
PEXT-10
Adaptor
Flue
Collar
Support straps or
support plate & ring
2’ min.
Firestop
Firestop
Firestop
3
2’ max
Support plate
& ring
Obstacle
PVTK1
Termination