Owner`s manual
Page 13
HWDF-Series Gas Fireplace
Part No. XG0190 - 071409
Installation
Figure 23. Multi-elbow installation. (The vent run ("L") must comply
with the Vent Graph, Figure 22b).
NOTES: All dimension lengths for vertical or horizontal runs are
measured from center of the vent pipe.
Venting runs must fall within the limits set by the venting
graph(seeFigure22b).
Installation Of Rear Vent DV
The following venting components are available for an HW38-DF in a
Rear Vent installation:
4" / 7" Venting 5" / 8" Venting
A - Termination MTO-3(3"Length)
MTO-3F(3"Length)
PTO-3(3"Length)
PTO-3F(3"Length)
B - Stucco Kits MSR(StuccoFrame)
BSR-4(4"BrickFrame)
BSR-6(6"BrickFrame)
MOSR(StuccoCan)
MSR(StuccoFrame)
BSR-4(4"BrickFrame)
BSR-6(6"BrickFrame)
MOSR(StuccoCan)
C - Flex Sections MFL-1(12"Section)
MFL-2(24"Section)
MFL-3(36"Section)
MFL-4(48"Section)
PFL-1(12"Section)
PFL-2(24"Section)
PFL-3(36"Section)
PFL-4(48"Section)
D - Rigid
Sections
MEXT-1(12"m/fSection)
EXT-18(18"f/fsection)
MEXT-2(24"m/fSection)
MEXT-3(36"m/fSection)
MEXT-4(48"m/fSection)
PEXT-1(12"m/fSection)
PXT-20(20"section)
PEXT-2(24"m/fSection)
PEXT-3(36"m/fSection)
PEXT-4(48"m/fSection)
E - Elbows MEL-90MM(m/m90°Elbow)
MEL-90FF(f/f90°Elbow)
MEL-90FM(f/m90°Elbow)
EEL-45(f/m45°Elbow)
PEL-90MM(m/m90°Elbow)
PEL-90FF(f/f90°Elbow)
PEL-90FM(f/m90°Elbow)
PEL-45FM(f/m45°Elbow)
Finishing Around the Fireplace
Combustible mantels and mouldings may be safely installed over the
topandonthefrontofthereplaceprovidedthattheydonotproject
beyond shaded area shown in Figure 24.Sidewallclearancesare3".
Combustiblesurroundsmaybeinstalledwith3"clearancetotheside
ofthereplaceasshowninFigure 25.
Fireplace Facing
Whenselectingthenishmaterialforyourreplace,itisimportantto
remember the following:
Ifthesurroundofthereplaceistobepaintedtomatchtheroomdecor,
heat-resistant paint must be provided . Also, decorative facing must not
extendpastthereplaceopeningatall,becauseitwillinterferewiththe
access to retainers for removal of glass door and access to the lower
compartment.
18"
50" min.
L Multi-elbow
Vent run.
Figure 23a. Installing the VSS Vinyl Shield.
Non-Combustible
Facing Material
Figure 24. Combustible mantles and facings.
Horizontal Run (in)
Mantels & Surrounds
NOTE: National Canadian Gas Association mantel test requirements
areforrehazardpreventiontocombustiblematerials.
New technology, to meet consumer and government demands for the
wise use of energy, has prompted us to manufacture many models of
replaceswhicharehot,fuelandenergyefcient.
Please be aware; temperatures over the mantel will rise above normal
roomtemperatureandwallsabovereplacemaybehottotouch.
Warning:
Whencoveringtheuppermetalportionofthereplace,upto6"(as
shown, Fig.24 & Fig.25)withanon-combustiblematerialPleaseNote:
The decorative facing materials may be subject to temperatures in excess
of 250° F. This should be considered when selecting facing materials.
We recommend careful consideration be given to the effects of elevated
mantel temperatures which may be in excess of product design, for
example: candles, plastic or pictures. This can cause melting, deformation,
discoloration or premature failure of T.V. and radio components.