Owner`s manual
H*38DF PRC Panorama Indoor Gas Fireplace
Page 14
XG0211 - 040912.1
Installation
WARNING:
An inspection of the explosion relief appers and door
MUST be made prior to lighting the replace. A faulty seal
on the door gasket and/or explosion ports will result in
products of combustion leaking into the living space and
may result in carbon monoxide poisoning.
Figure 14. H38PR* or HL38PR* Rear Vent Venting Graph for wall mounted
terminations.
Notes Wall Mounted Terminations: REAR VENT
All dimension lengths for vertical or horizontal runs are measured
from center of the vent pipe.
Venting runs must fall within the limits set by the venting graphs,
see Figure 14 or 14a.
Fireplace must be converted to Rear Vent conguration prior to
running vent, see Figure 8 and 8a.
The Venting Graph
Measure the vertical height from the replace hearth to the centre of
the termination and the horizontal run from the replace ue collar to
the wall ange of the termination. Plot on the Venting Graph Figure 14
or 14a with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 114" and the horizontal
run to the wall ange of the vent termination is 126", this would be
an acceptable installation.
Example B: (Unacceptable Installation)
If the vertical dimension from the hearth is 66" and the horizontal
run to the wall ange of the vent termination is 84", this would
NOT be an acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the oor of the replace is 72" and
the horizontal run to the wall ange of the vent termination is 144",
this would NOT be an acceptable installation.
Figure 15. H38PR* or HL38PR* Straight run, Rear Vented, wall mounted
termination. The vent run must comply with the Venting Graph for Rear vent,
wall mounted terminations Figure 14. Note: HP38PR* CANNOT be straight
run, rear vented with a wall mounted termination.
33 1/2”
PXT Extension
RHS101 Heat
Shield
Termination
Hearth
Exterior
Wall
NOTE:
12” MAX. horizontal
run with no vertical lift.
12” MAX.
33”
12”
A
B
C
59”
46”
Unacceptable vent run
within shaded area.
Acceptable vent run
within non-shaded area.
If your installation does not fall with-
in the venting graph parameters,
please contact a local Montigo
dealer for Power Venting options.
42
”
59”
A
C
B
Acceptable vent run
within non-shaded area.
.
Unacceptable vent run
within shaded area.
If your installation does not fall with-
in the venting graph parameters,
please contact a local Montigo
dealer for Power Venting options.
Figure 14a. HP38PR*Rear Vent Venting Graph for wall mounted terminations.