Specifications

ZVC48LSSMONOGRAM 48" CUSTOM HOOD INSERT
Listed by
Underwriters
Laboratories
Product Specification Revised 1/18
Opening
The custom canopy must be sized to fit the insert sleeve.
Construct the canopy with an opening that is:
38-3/4"W x 13-3/16"D
The opening must be constructed of 3/4" thick material
to allow the sleeve locking clips to engage.
A stainless steel liner is shipped with each hood insert.
This non-combustible liner protects the underside of the
canopy.
CUSTOM LINER
If you are not using the supplied liner, you may construct
a custom non-combustible liner. Use the supplied liner as
a template. The opening must be 38-3/4"W x 13-3/16"D.
3/4" thick material must surround the opening to allow
the sleeve locking clips to engage. The insert sleeve
inside the cabinet should be positioned 1/2" from the rear
wall so that the center of the 8" duct is 5-1/2" from the
rear wall.
REMOTE LOCATION FOR THE CONTROL
The control may be removed from the hood and
installed into a wall or countertop. A 30-ft length of
wire is supplied to accommodate most installations. A
blanking plate covers the opening when the controls
are removed. The overall size of the control is 4-1/4"
wide and 2-1/4" deep.
3'-11/16"
1'-11/16"
Control Cutout
We recommend that the cutout in granite or other hard
surfaces be made before the countertop is installed.
CUSTOM INSERT LINER DIMENSIONS AND SPECIFICATIONS (IN INCHES)
OUTSIDE DIMENSIONS
THE INSERT SLEEVE
THE SUPPLIED LINER