Specifications

ZSA1202JSSMONOGRAM 120 ABOVE-THE-COOKTOP ADVANTIUM® OVEN
For answers to your Monogram, GE Café
Series, GE
Profile
Series or GE Appliances product questions,
visit our website at geappliances.com or call GE
Answer Center
®
Service, 800.626.2000.
Product Specification Revised 1/18
Grille
FILTER KIT ACCESSORY
Filter Kit
JX81D–Recirculating Charcoal Filter Kit
To be used when the Advantium oven
cannot be vented to the outside.
Duct Equivalent
Rectangular-To-Round
Transition Adaptor
5 Ft.
Wall Cap 40 Ft.
90° Round Elbow 10 Ft.
45° Round Elbow 5 Ft.
90° Rectangular Elbow 25 Ft.
45° Rectangular Elbow 5 Ft.
Roof Cap 24 Ft.
Hood Exhaust Duct
Outside ventilation
requires a HOOD
EXHAUST DUCT. Read
the following carefully.
EXHAUST
CONNECTION:
The hood exhaust has
been designed to mate
with a standard 3-1/4" x
10” rectangular duct.
If a round duct is
required, a rectangular-
to-round transition
adaptor must be used.
Do not use less than a
6" diameter duct.
REAR EXHAUST:
If a rear or horizontal
exhaust is to be used,
care should be taken
to align exhaust with
the space between
studs, or wall should be
prepared at the time it is
constructed by leaving
enough space between
the wall studs to
accommodate exhaust.
MAXIMUM DUCT
LENGTH:
For satisfactory air
movement, the total
duct length of 3-1/4"
x 10” rectangular or
6" diameter round duct
should not exceed 140
equivalent feet.
ELBOWS, TRANSITIONS,
WALL AND ROOF
CAPS, etc., present
additional resistance
to airflow and are
equivalent to a section
of straight duct which is
longer than their actual
physical size. When
calculating the total
duct length, add the
equivalent length of all
transitions and adaptors
plus the length of all
straight duct sections.
The chart below shows
the approximate feet
of equivalent length of
some typical ducts.
NOTES