Specifications

To connect grounding jumper:
Disconnect restraining clip holding jumper.
Connect green jumper to open terminal on
neutral (white) portion of the terminal block.
Connect Here
Red
White
Black
Terminal Block
Green
NEMA 14-50R
Receptacle
Gas Supply
Flex Line
to Range
8for 30Models
12for 36Models
16for 48Models
Electrical
Supply
4
1-1/2
2Maximum
Protrusion From
Wall For Gas Supply
4for 30/36Models
8for 48Models
12
POWER SUPPLY LOCATIONS
Gas Supply:
The natural gas models are designed to operate at 5"
water column pressure. A regulator is required at the
natural gas source to provide a maximum of 7" water
pressure to the cooktop regulator.
The liquid propane models are designed to operate at
10" water column pressure. A regulator is required at
the LP source to provide a maximum of 14" water
pressure to the cooktop regulator.
These gas ranges are supplied with 1/2" NPT female
gas connection located at the left rear corner.
A minimum 5/8" dia. metal flexible line is required.
Locate pipe stub on the back wall as illustrated.
– Use 5-foot, 5/8" long flexible gas supply line.
Install a manual shut-off valve in the gas line, in an
easily accessible location.
7
If the electrical service provided does not meet the
above specifications, it is recommended that a
licensed electrician install an approved outlet.
Locate the electric supply as illustrated.
WARNING: The range is
equipped for use with an electrical supply
which uses a separate grounding conductor
(4 wire system).
If this range must be connected to an electrical
system which utilizes a single conductor for ground
and neutral (3 wire system), the grounding jumper at
the terminal block must be connected. The grounding
jumper is located behind the front kick panel.
AVERTISSEMENT :
Étant donné sa conception, la cuisinière
exige que l’alimentation électrique soit
dotée d’un conducteur de terre distinct (système à
4 fils).
Si cette cuisinière doit être connectée à un système
électrique qui utilise un conducteur simple pour la
mise à la terre et le conducteur neutre (système à
3 fils), il faut alors connecter le cavalier de terre sur
la plaque à bornes. Le cavalier de terre est situé
derrière le panneau de protection frontal.
Electric Supply:
These ranges must be supplied with 208/240 volt, 60 Hz.,
and connected to an individual, properly grounded
branch circuit protected by a circuit breaker or time
delay fuse (50 amp for 48" ranges, 30 amp for 36" ranges
and 25 amps for 30" ranges). The receptacle must be
a NEMA 14-50R device to accept the 4-prong plug
supplied with the range.
4for 30″/36
Models
8for 48
Models
Installation Preparation