User`s guide

On Bootup: The cell light begins ashing red. The ashing switches to green and
nally lands on a solid green when the link to the cell network is established. Next, the
middle light ashes green and then lands on solid green when the link to the server is
established. The wireless sensor light turns green indicating the gateway is ready to
listen to sensor trafc.
During Operation: All lights are solid green. Activity from a sensor will cause the wire-
less sensor light to ash instantly. When the gateway is deliver messages to the server,
the cell light may illuminate and go through the sequence of acquiring a link to a tower if
it is not currently connected. The middle light ashes green on the gateway’s heartbeat,
or when an urgent message needs delivery.
2. Cellular Gateway Controls
Control Button
A short press of the control button while lights are all green, will force immediate
communication to server and exchange all sensor data currently stored in memory.
Press and hold to reset the gateway to factory settings (hold until all lights go red).
This resets the gateway heartbeat to 60 minutes. You will need to login to the online
system after resetting the gateway to recongure the gateway to your desired settings.
Note: If the gateway LEDs do not turn green, you may have a connectivity issue. Wait a few
minutes to see if the lights turn green. If they do not, power cycle the device by disconnecting then
reconnecting the power on standard gateways or toggling the power switch on gateways with bat-
tery backup. If it still does not connect, reset the device to factory settings. If there is still an issue,
contact Monnit customer support. If all three lights look amber, then there is an internal hardware
problem. If, left to right, the lights are red-green-green, there is a cell modem issue. If red-red-
green, there is a memory issue. For all of these cases, you will need to contact Monnit support.
3. Conguring The Cellular Gateway
The cellular gateway collects data from all sensors within range and is precongured
to batch deliver the sensor messages to the online system at the specied heartbeat
(every 60 minutes by default factory settings).
You can access gateway settings by clicking on “View Gateways” in the top bar of the
“Overview” page. Clicking on a gateway in the list, opens the detail view. Click on the
“Edit” tab to access the gateway’s settings.