User`s guide

WD_CNT 40004 Wireless Device Count – Value that can be
read to discover the number of registered
sensors are congured to operate on the
gateway. A value 0 – 100 is permitted.
(READ-ONLY)
Example Value: 0 (no sensors registered,
factory reset condition)
Example Value: 10 (10 Registered device)
The following table represents the gateway’s Wireless Device
List, or the current devices that the gateway is congured to
communicate with. These registers can be read to discover
the state of the list. If any register is written to, the device as-
sociated with that address is erased and these registers are
zeroed out. The serial identiers are formatted as a UInt32,
therefore two contiguous registers must be read to extract the
full value.
ADDRESS FORMULA = 40101 + (2*WDL_SLOT)
List entries can be as follows:
0xFFFFFFFF: EMPTY
0x00000000: ERASED, Unusable
until a Network Reset
Otherwise, a real device is registered
Example:
Register Name Address Register Name Address
WDL [0] 40101 WD [99] 40299
Bring Sensors Online
To bring your sensors online, insert the battery into the sen-
sors. Once the battery is inserted, the wireless device does a
scan to look for the network. As long as the gateway is AC-
TIVE, the sensor will link up to the network.
+