User`s guide
WD_CNT 40004 Wireless Device Count – Value that can be
read to discover the number of registered
sensors are congured to operate on the
gateway. A value 0 – 100 is permitted.
(READ-ONLY)
Example Value: 0 (no sensors registered,
factory reset condition)
Example Value: 10 (10 Registered device)
The following table represents the gateway’s Wireless Device
List, or the current devices that the gateway is congured to
communicate with. These registers can be read to discover
the state of the list. If any register is written to, the device as-
sociated with that address is erased and these registers are
zeroed out. The serial identiers are formatted as a UInt32,
therefore two contiguous registers must be read to extract the
full value.
ADDRESS FORMULA = 40101 + (2*WDL_SLOT)
List entries can be as follows:
• 0xFFFFFFFF: EMPTY
• 0x00000000: ERASED, Unusable
until a Network Reset
• Otherwise, a real device is registered
Example:
Register Name Address Register Name Address
WDL [0] 40101 WD [99] 40299
Bring Sensors Online
To bring your sensors online, insert the battery into the sen-
sors. Once the battery is inserted, the wireless device does a
scan to look for the network. As long as the gateway is AC-
TIVE, the sensor will link up to the network.
+
_
PAGE 8