User`s guide

Verify Communication Settings
The Serial MODBUS supports 2 transmission modes: RTU
and ASCII. The default communication is MODBUS-RTU, 8
data bits, No Parity, 1 Stop bit (8-N-1), 19200 baud. The MOD-
BUS slave ID or Modbus address is 99 or 0x63.
The following commands (Function Codes) are supported:
FC = 1: Read Coils
FC = 5: Write Single Coil
FC = 15: Write Multiple Coils
FC = 3: Read Holding Registers
FC = 6: Write Single Register
FC = 16: Write Multiple Registers
All other commands, exceptions, or other interface features
are not supported.
Perform Communication Verication
Poll the WACTIVE gateway coil at address 1. This should
return False if no sensors have been registered yet.
Poll the Gateway ID registers 40002-40003 and verify the
number returned matches the Gateway ID on the bottom of
your serial MODBUS gateway (4 digit number near the bar
code).
If the device times-out or gives some other error, please see
the Monnit Serial MODBUS Gateway User’s Manual for ex-
ample MODBUS communications.
Change Communication Settings
If you prefer to use different communication settings than the
default, follow the instructions on the next page. Otherwise,
skip to the next section.