User`s guide

- 24 -
Example Value: 0 (no sensors
registered, factory reset condition)
Example Value: 10 (10 Registered
device)
OP_CHAN
40005
4 Operating channel designator
reports the wireless channel in
use. Value of 0-25 is permitted
(READ-ONLY)
BAUDRATE
40006
5 Designates the baud rate used by
the MODBUS interface. After
modifying this register, a gateway
reset must be performed before
changes can take effect.
Value Represented Baud
Selected
0 2400
1 4800
2 9600
3 (DEFAULT) 19200
4 38400
5 57600
6 115200
COMMODE
40007
6 Designates the operating mode
used by the MODBUS interface.
After modifying this register, a
gateway reset must be performed
before changes can take effect.
Value Meaning
0 RTU : 8-N-2
1 (DEFAULT) RTU : 8-N-1
2 RTU : 8-E-1
3 RTU : 8-0-1
4 ASCII : 7-N-2
5 ASCII : 7-E-1
6 ASCII : 7-O-1
COMADDR
40008
7 Designates the MODBUS Address
used in the communications
interface. Values range from 1-
247. Default value is 95.