User`s guide

- 23 -
PENDING_CFG
2
True (1) denotes that one or more registers
have been modified from their original values
(located on the remote device).
False (0) denotes that the no local registers
contain configurations that are different from
the remote device.
Writing True (1) to this coil will cause the local
configuration parameters contained in the gate-
way to be sent to the remote device. (
FORCE
OVERWRITE).
Writing False (0) to this coil will
be ignored.
Coil resets automatically when remote
configuration changes have been confirmed.
FORCE_REMOTE_
SYNC
3
Always read as False (0). If set to True (1),
then the wireless device’s local registers will be
cleared and the remote configurations will be
retrieved.
Ref.3 - Gateway Registers
The following table represents the supported gateway settings and
their corresponding properties.
Register Name
Function
Code
Raw
Address
Description
VERSION
40001
0 Designates the FW Version of the
Gateway.
(READ-ONLY)
Example Value: 0x3000
(Read 3.0.0.0)
ID_H
40002
1
ID_L
40003
2
Gateway’s globally-unique
identifier.
(READ-ONLY)
Combine an ID_H and ID_L to
form UInt32 number.
WD_CNT
40004
3 Wireless Device Count – Value
that can be read to discover the
number of registered sensors are
configured to operate on the
gateway. A value
0 – 50
is
permitted.
(READ-ONLY)