User`s guide
- 20 -
Reference Section
Complete Gateway Features and Resource Mapping
Reference
Through the MODBUS interface, the following features are
available for access by a MODBUS master. All coils and registers
are available for read or write access through the MODBUS
address mapping presented here.
Ref.1 - Gateway Coils
The following table represents the supported gateway specific
coils. These are intended to report the status, control the state, or
trigger events on the gateway.
Coil Name Function
Code
Raw
Address
Description
WACTIVE
1
0
True (1) denotes that the system is
configured sufficiently to
communicate to the sensor.
False (0) denotes that the Wireless
system is not active.
Causes for this include:
- No Registered Sensors.
RST_DEVICE
2
1
Writing True (1) to this coil will force
a device reset and cleans out all
current status. Always read as False
(0).
RST_WNET
3
2
Writing True (1) to this coil will force
a
Wireless Network Reset and reform
the operating network setting based
on CHANM and NETID (in Gateway
Registers). Always read as False (0).
RST_COM
4
3
Writing True (1) to this coil will force
the ADDRESS, COMMODE, and
BAUDRATE to defaults. Always read
as False (0). After setting this coil to
true, a device reset command must
be issued before any of the new
settings will take effect.